Cerbo GX Manual

7. VE.Bus Inverter/charger monitoring
7.1. Input current-limiter setting
'Overruled by remote' setting in VEConfigure
This chapter explains the implications of enabling or disabling user control of the input current-limiter setting, as seen here in the
menu:
The limit as set by the user in the Cerbo GX will be applied to all inputs where 'Overruled by remote', configured with VictronCon-
nect or VEConfigure, is enabled:
Using the example of a boat with two AC inputs and a Quattro where:
1. A Genset capable of delivering 50A is connected to input 1;
2. Shore power is connected to input 2. (Available power depends on the rating of the harbour power-supply.)
Configure the system exactly as in above VEConfigure screenshot. Input 1 has priority over input 2, therefore the system will au-
tomatically connect to the genset whenever it is running. The fixed input current limit of 50A will be applied. And when the genset
is not available, and mains is available on input 2, the Quattro will use the input current limit as configured in the Cerbo GX.
Two more examples: (In both cases if you disable 'Overrule by remote', setting a current limit in the Cerbo GX will have no effect.
And if you enable 'Overrule by remote' for both inputs, the current limit set in the Cerbo GX will be applied to both inputs.)
Systems where it is not possible to control the input current limit
Cerbo GX Manual
34