MultiPlus-II to MultiGrid and MultiPlus comparison

1
07-05-2019
MultiPlus-II
Comparison sheet
Specifications
1. Block diagrams
MultiPlus-II
24/3000/70-32
PMP242305010
HW rev. 01 and up
MultiPlus-II
48/3000/35-32
PMP482305010
HW rev. 08 and up
MultiPlus-II
48/5000/70-50
PMP482505010
HW rev. 03 and up
MultiPlus-II
48/3000/35-32
PMP482305000
HW rev. < 08
MultiPlus-II
48/5000/70-50
PMP482505000
HW rev. < 03
MultiGrid
48/3000/35-50
MultiPlus
48/3000/35
PowerControl & PowerAssist
Transfer switch
32A
32A
50A
32A
50A
50 A
16A or 50A
DC Input voltage range
19 33 V
38 66 V
Output
Cont. output power at 25°C (3)
3000 VA
3000 VA
5000VA
3000 VA
5000VA
3000 VA
Cont. output power at 25°C
2400 W
2400 W
4000W
2400 W
4000W
2400 W
Cont. output power at 40°C
2200 W
2200 W
3700W
2200 W
3700W
2200 W
Cont. output power at 65°C
1700 W
1700 W
3000W
1700 W
3000W
1700 W
Maximum apparent feed-in power
2500VA
2500VA
4000VA
2500VA
4000VA
2500VA
Peak power
5500 W
5500 W
9000W
5500 W
9000W
6000 W
Maximum efficiency
95 %
95 %
96%
95 %
96%
95 %
Zero load power
11 W
11 W
18W
11 W
18W
25 W
Zero load power in AES mode
7 W
7 W
12W
7 W
12W
20 W
Zero load power in Search mode
2 W
2 W
2W
2 W
2W
12 W
AC Input
Charge voltage 'absorption'
28,8 V
57,6 V
Charge voltage 'float'
27,6 V
55,2 V
Storage mode
26,4 V
52,8 V
Maximum battery charge current (4)
70 A
35 A
70 A
35 A
70 A
35 A
Charge current starter battery (A)
4 A
n.a.
Battery temperature and voltage
sensor
Yes Yes
Yes
VE.Bus Smart dongle (optional) Yes
Auxiliary output
Yes (32 A)
Relay with 2 minutes turn on delay
Yes (32 A)
Directly connected to the AC input
Yes (16 A)
Relay with 2 minutes turn on delay
External current sensor (optional)
50A
50A
100A
50A
100A
No
Programmable relay (5)
Protection (2)
VE.Bus communication port
General purpose com. ports
Remote on-off Yes, 2 pole
Yes, 3 pole
(Incl. remote Charger only)
Operating temperature range
Humidity (non-condensing)
Material & Colour
Steel, blue RAL 5012
Aluminium, blue RAL 5012
Protection category
IP22
IP20
Battery-connection
M8 Bolts
Four M8 bolts
230 V AC-connection
Weight
18 kg
18 kg
29 kg
18 kg
29 kg
18 kg
Dimensions (hxwxd)
506 x 275 x 147 mm
506 x 275 x 147 mm
565 x 323 x 148 mm
499 x 268 x 141 mm
560 x 320 x 141 mm
362 x 258 x 218 mm
1) Can be adjusted to 60 Hz
2) Protection key:
a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high
f) 230 VAC on inverter output g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function
AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC

Summary of content (5 pages)