Manual

12
7. Technical specifications
MultiPlus
12/3000/120-50 120V
24/3000/70-50 120V
PowerControl / PowerAssist
Yes
AC input
Input voltage range: 95-140VAC; Input frequency: 45 65Hz; Power factor: 1
Maximum feed through current
50
Minimum AC supply current capacity for
PowerAssist (A)
7,5
INVERTER
Input voltage range (V DC)
9,5 17
19 33
Output (1)
Output voltage: 120 VAC ± 2% Frequency: 60 Hz ± 0,1%
Cont. output power at 25°C / 77°F (VA) (3)
3000
3000
Cont. output power at 25°C / 77°F (W)
2400
2400
Cont. output power at 40°C / 104°F (W)
2200
2200
Cont. output power at 65°C / 150°F (W)
1700
3000
Peak power (W)
6000
6000
Maximum efficiency (%)
93
94
Zero-load power (W) 20 20
Zero-load power in AES mode (W) 15 15
Zero-load power in Search mode (W)
8
10
CHARGER
AC Input
Input voltage range: 95-140VAC Input frequency: 45 65Hz Power factor: 1
Charge voltage 'absorption' (V DC)
14,4
28,8
Charge voltage 'float' (V DC)
13,8
27,6
Storage mode (V DC)
13,2
26,4
Charge current house battery (A) (4)
120
70
Charge current starter battery (A)
4
Battery temperature sensor
Yes
GENERAL
Auxiliary output
Max. 32A Switches off when no external AC source available
Programmable relay
(5)
Yes, 3x
Protection (2)
a - g
VE.Bus communication port
For parallel and three phase operation, remote monitoring and system integration
General purpose comm. port
Yes, 2x
Common Characteristics
Operating temp.: -40 to +65°C/ -40 - 150°F (fan assisted cooling)
Humidity (non-condensing) : max 95%
ENCLOSURE
Common Characteristics
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Battery-connection
M8 bolts (2 plus and 2 minus connections)
120V AC-connections
Screw terminals 13mm² (6 AWG)
Weight (kg)
19
Dimensions (hxwxd in mm)
362 x 258 x 218
STANDARDS
Safety
UL1741, UL458, EN 60335-1, EN 60335-2-29
Emission / Immunity
EN 55014-1, EN 55014-2, EN 61000-3-3
Automotive Directive
2004/104/EC
1) Can be adjusted to 50Hz;
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 120VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general alarm, DC undervoltage or genset start/stop function