Manual

6
Charger
Inverter
The inverter has switched off due to
the electronics temperature being
too high.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
Inverter
-If the LEDs are flashing alternately,
the battery is nearly exhausted and
the nominal output is exceeded.
-If "overload" and "low battery" flash
simultaneously, the ripple voltage
on the battery terminals is too high.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
Inverter
The inverter switched off due to
excess ripple voltage on the battery
terminals.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Battery Charger
Charger
Inverter
The AC input voltage is switched
through and the charger operates in
bulk mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
Inverter
The mains voltage is switched
through and the charger is on.
The set absorption voltage,
however, has not yet been reached.
(BatterySafe mode)
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature
Charger
Inverter
The mains voltage is switched
through and the charger operates in
absorption mode.
mains on
on
inverter on
Bulk
overload
off
absorption
low battery
charger
only
Float
temperature