User manual
14
5. Configuration
• Settings may only be changed by a qualified electrical engineer.
• Read the instructions thoroughly before implementing changes.
• During setting of the charger, the DC fuse in the battery connections must
be removed.
5.1 Standard settings: ready for use
On delivery, the Quattro is set to standard factory values. In general, these settings are selected for single-unit operation.
Settings, therefore, do not require changing in the event of stand-alone use.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard Quattro factory settings
Inverter frequency 50 Hz
Input frequency range 45 - 65 Hz
Input voltage range 180 - 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
AES (Automatic Economy Switch) off
Ground relay on
Charger on/ off on
Charging characteristics four-stage adaptive with BatterySafe mode
Charging current 75% of the maximum charging current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 14.4 / 28.8 / 57.6 V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 13.8 / 27.6 / 55.2 V
Storage voltage 13.2V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection on
Generator (AC-in-1) / shore current (AC-in-2) 30A/16A (current limit for PowerControl and PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Multi-functional relay alarm function
VirtualSwitch controls the multi-functional relay
PowerAssist on
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software
configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1
(priority input) or AC-in-2. The output frequency is then equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1 (priority input)
or on AC-in-2. The output voltage is then equal to the input voltage input.
Adjustability: Lower limit: 180 - 230V
Upper limit: 230 - 270V