Specifications
6
Option 2b: Two stacked 120V or 120/240V Quattro’s or Multi’s with additional 120/240V input autotransformer
AC source (input) Does system connect to
AC source?
Power for battery charging
taken from
Output
120/240V 3wire + ground
(split phase 60Hz)
Yes (neutral wire should not be
connected)
240V
120/240V 3wire + ground 60Hz
120/208V 3wire + ground
(three phase two leg 60Hz)
Yes (neutral wire should not be
connected)
208V
104/208V 3wire + ground 60Hz
(180 degrees split phase output)
240V 2 wire + ground
(single phase 60Hz)
Yes (neutral comes from 120/240V
autotransformer
240V
120/240V 3wire + ground 60Hz
230V 2 wire + ground
(single phase 50Hz)
Yes (neutral comes from 120/240V
autotransformer
230V
115/230V 3wire + ground 50Hz
208V 2 wire + ground
(single phase 60Hz)
Yes (neutral comes from 120/240V
autotransformer
208V
104/208V 3wire + ground 60Hz
120V 2 wire + ground
(single phase 60Hz)
No
120/240V 3wire + ground 60Hz
Not available (no input) No
120/240V 3wire + ground 60Hz
(inverter mode)
PowerControl and PowerAssist functionality will be available on the single phase input of the auto transformer
Figure 2b: Two stacked 120/240V Quattro’s with input autotransformer (option 2b)
Ground cables and interconnection for synchronization not shown
Connection to second AC source not shown.