Specifications

16
5. Configuration
Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the DC fuse in the battery connections must
be removed.
5.1 Standard settings: ready for use
On delivery, the Quattro is set to standard factory values. In general, these settings are selected for single-unit operation.
Settings, therefore, do not require changing in the event of stand-alone use.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the
manufacturer's documentation, or to your battery supplier!
Standard Quattro factory settings
Inverter frequency 60 Hz
Input frequency range 45 - 65 Hz
Input voltage range (neutral to L1-1, L1-2) 94 - 143 VAC (input voltage is monitored between neutral and L1-1, L1-2
only)
Inverter output voltage 120 VAC
Stand-alone / parallel / 3-phase stand-alone
AES (Automatic Economy Switch) off
Ground relay on
Charger on/ off on
Charging characteristics four-stage adaptive with BatterySafe mode
Charging current 75% of the maximum charging current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 14.4 / 28.8 / 57.6 V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 13.8 / 27.6 / 55.2 V
Storage voltage 13.2 / 26.4 / 52.8 V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection on
Generator (AC-in-1) / shore current (AC-in-2) 50A/30A
(= adjustable current limit for PowerControl and PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Multi-functional relay alarm function
VirtualSwitch controls the multi-functional relay
PowerAssist on
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the
software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 60Hz; 50Hz
Input frequency range
Input frequency range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on L1-1 of
AC-in-1 (priority input) or L1-2 of AC-in-2. Once synchronised, the output frequency will be equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on L1-1 of AC-in-1
(priority input) or on L1-2 of AC-in-2. After the back feed relay has closed, output voltage will be equal to input voltage.
Adjustability: Lower limit: 94 - 120V
Upper limit: 120 - 143V
Inverter voltage
Output voltage of the Quattro in battery operation.
Adjustability: 95 – 128V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devices in parallel)
create a split-phase system (available only on Quattro units with 120V output voltage)
create a 3-phase system.
To this end, the devices must be mutually connected with RJ45 UTP cables. Standard device settings, however, are such that
each device operates in stand-alone operation. Reconfiguration of the devices is therefore required.