Specifications
25
EN Appendix
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the
leader L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
ds8-ds7
Absorption
voltage
Float
voltage
Storage
voltage
Suitable for
off off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
off on
14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
on off
14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
AGM Victron Deep Discharge
Tubular plate traction or OPzS
batteries in semi-float mode
AGM spiral cell
on on
15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
Tubular plate traction or OPzS
batteries in cyclic mode
ds6: absorption time 8 or 4 hours on = 8 hours off = 4 hours
(not relevant for L2, L3)
ds5: adaptive charging characteristic on = active off = inactive
(inactive = fixed absorption time)
(not relevant for L2, L3)
ds4: dynamic current limiter on = active off = inactive
ds3: UPS function on = active off = inactive
ds2: converter voltage on = 120V off = 115V
ds1: converter frequency on = 50Hz off = 60Hz
(not relevant for L2, L3)
(note: the wide input frequency range (45-65z) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are always in
‘off’ position and are not related to the actual settings in the microprocessor).
DS-8 Ch. voltage off
DS-7 Ch. voltage on
DS-6 Absorpt. time on
DS-5 Adaptive ch. on
DS-4 Dyn. Curr. limit off
DS-3 UPS function: on
DS-2 Voltage on
DS-1 Frequency off
DS-8 off
DS-7 off
DS-6 on
DS-5 on
DS-4 off
DS-3 off
DS-2 on
DS-1 off
DS-8 on
DS-7 off
DS-6 on
DS-5 on
DS-4 on
DS-3 off
DS-2 off
DS-1 off
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 60Hz
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Absorption time: 8 h
5 Adaptive charging: on
4 Dyn. current limit: off
3 UPS function: off
2 Voltage: 120V
1 Frequency: 60Hz
Step 2
Example 3:
8, 7 AGM 14,7V
6 Absorption time: 8 h
5 Adaptive charging: on
4 Dyn. current limit: on
3 UPS function: off
2 Voltage: 115V
1 Frequency: 60Hz
Step 2
Example 4:
8, 7 Tubular-plate 15V
6 Absorption time: 4 h
5 Fixed absorption time
4 Dyn. current limit: off
3 UPS function: on
2 Voltage: 115V
1 Frequency: 50Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of
the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the ’other settings’ can always be recovered.