Specifications
30
1) Can be adjusted to 50 Hz
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. Input voltage ripple too high
g. 120VAC on inverter output
3) Non linear load, crest factor 3:1
4) At 80ºF / 25°C ambient
5) Multipurpose relay which can be set for
general alarm, DC under voltage or genset
start signal function
8. Technical specifications
Quattro
12/5000/200
120/240V
24/5000/120
120/240V
48/5000/70
120/240V
PowerControl / PowerAssist Yes Yes Yes
Integrated Transfer switch Yes Yes Yes
AC inputs (2x)
Input voltage: 120 V or 120/240 V Input frequency: 45 – 65 Hz
Power factor: 1
Maximum feed through current
120V single phase: 60 A 120V dual in phase: 60 A total
120/240 V split phase: 60 A each leg
Minimum PowerAssist current
11A (AC-in-1 only)
INVERTER
Input voltage range (V DC) 9,5 – 17 19 – 33 38 – 66
Output (pure sinewave) Output voltage: 120 VAC ± 2% Frequency: 60 Hz ± 0,1% (1)
Cont. output power at 77ºF/25°C
(VA) (5)
5000 5000 5000
Cont. output power at 77ºF/25°C
(W)
4000 4250 4250
Cont. output power at 100ºF/40°C
(W)
3000 3350 3350
Peak power (W) 8000 10.000 10.000
Maximum efficiency (%) 92 94 95
Zero-load power (W) 25 30 30
Load shedding All 240V loads are switched off when in inverter mode
CHARGER
Charge voltage 'absorption'
(V DC)
14,4 28,8 57,6
Charge voltage 'float' (V DC) 13,8 27,6 55,2
Storage mode (V DC) 13,2 26,4 52,8
Charge current house battery (A)
(4)
200 120 70
Charge current starter battery (A) 4
Battery temperature sensor Yes
GENERAL
Multi purpose relay (6) Yes Yes Yes
Protection (2) a – g
Common Characteristics
Operating temp.: 0 to 120°F (-20 to +50°C)
Humidity (non condensing) : max 95%
ENCLOSURE
Common Characteristics Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Battery-connection Four M8 bolts (2 plus and 2 minus connections)
120/240 V AC-connection Screw terminals 13mm² (6 AWG)
Weight 66 lb 30 kg
Dimensions (hxwxd) 17,5 x 13,0 x 9,6 inch 444 x 328 x 240 mm
STANDARDS
Safety EN 60335-1, EN 60335-2-29
Emission / Immunity EN55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3