Product Manual

26
25. Clear high starter voltage relay - 702 and -712 only
When the auxiliary voltage falls below this value, the relay will open (after a delay, depending
on setting 14 and/or 15). This value needs to be less than or equal to the previous parameter.
Default Range Step size
0V 0 95V 0,1V
_______________________________________________________________
26. High temperature relay - 702 and -712 only
When the battery temperature rises above this value for more than 10 seconds, the relay will
be activated.
27. Clear high temperature relay - 702 and -712 only
When the temperature falls below this value, the relay will open (after a delay, depending on
setting 14 and/or 15). This value needs to be less than or equal to the previous parameter.
28. Low temperature relay - 702 and -712 only
When the temperature falls below this value for more than 10 seconds, the relay will be
activated.
29. Clear low temperature relay - 702 and -712 only
When the temperature rises above this value, the relay will open (after a delay, depending on
setting 14 and/or 15). This value needs to be greater than or equal to the previous parameter.
See setting 67 for choosing between °C and °F.
Default Range Step size
0°C -99 99°C 1°C
0°F -146 210°F 1°F
_______________________________________________________________
30. Mid voltage relay - 702 and -712 only
When the mid-point voltage deviation rises above this value for more than 10 seconds, the
relay will be activated. See section 5.2 for more information about the mid-point voltage.
31. Clear mid voltage relay - 702 and -712 only
When the mid-point voltage deviation falls below this value, the relay will open (after a delay,
depending on setting 14 and/or 15). This value needs to be less than or equal to the previous
parameter.
Default Range Step size
0% 0 99% 0,1%