4.2.3 Alarm-Buzzer settings
Remark: thresholds are disabled when set at 0
_____________________________________________________________
32. Alarm buzzer
When set, the buzzer will sound an alarm. After a button is pressed the buzzer will stop
sounding. When disabled the buzzer will not sound an alarm.
Default Range
ON ON/OFF
______________________________________________________________
33. Low SOC alarm
When the state-of-charge falls below this value for more than 10 seconds the low SOC
alarm is turned on. This is a visual and audible alarm. It does not energize the relay.
34. Clear low SOC alarm
When the state-of-charge rises above this value, the alarm is turned off. This value needs to
be greater than or equal to the previous parameter.
Default Range Step size
0% 0 99% 1%
______________________________________________________________
35. Low voltage alarm
When the battery voltage falls below this value for more than 10 seconds the low voltage
alarm is turned on. This is a visual and audible alarm. It does not energize the relay.
36. Clear low voltage alarm
When the battery voltage rises above this value, the alarm is turned off. This value needs to
be greater than or equal to the previous parameter.
37. High voltage alarm - When the battery voltage rises above this value for more than
10 seconds the high voltage alarm is turned on. This is a visual and audible alarm. It does
not energize the relay.
38. Clear high voltage alarm - When the battery voltage falls below this value, the
alarm is turned off. This value needs to be less than or equal to the previous parameter.
BMV-700 / BMV-702 / BMV-712 Smart
Default Range Step size
0V 0 95V 0,1V
BMV-700H
Default Range Step size
0V 0 384V 0,1V
_______________________________________________________________
39. Low starter voltage alarm - 702 and -712 only
When the auxiliary (e.g. starter battery) voltage falls below this value for more than
10 seconds the alarm will be activated. This is a visual and audible alarm. It does not energize
the relay.