Product Card

Our LFP batteries have integrated cell balancing and cell monitoring. Up to 5 batteries can be paralleled and up to four batteries can be
series connected, so that a 48V battery bank of up to 1500Ah can be assembled. The cell balancing/monitoring cables can be daisy-
chained and must be connected to a Battery Management System (BMS).
Battery Management System (BMS)
The BMS will:
1. Disconnect or shut down the load whenever the voltage of a battery cell decreases to less than 2,5V.
2. Stop the charging process whenever the voltage of a battery cell increases to more than 4,2V.
3. Shut down the system whenever the temperature of a cell exceeds 50°C.
See the BMS datasheets for more features
Battery specification
VOLTAGE AND CAPACITY
LFP-
Smart
12,8/60
LFP-
Smart
12,8/100
LFP-
Smart
12,8/150
LFP-
Smart
12,8/160
LFP-
Smart
12,8/200
LFP-
Smart
12,8/200-a
LFP-
Smart
12,8/300
LFP-
Smart
25,6/200
Nominal voltage 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 25,6V
Nominal capacity @ 25°C*
60Ah 100Ah 150Ah 160Ah 200Ah 200Ah 300Ah 200Ah
Nominal capacity @ 0°C*
48Ah 80Ah 125Ah 130Ah 160Ah 160Ah 240Ah 160Ah
Nominal capacity @ -20°C* 30Ah 50Ah 75Ah 80Ah 100Ah 100Ah 150Ah 100Ah
Nominal energy @ 25°C* 768Wh 1280Wh 1920Wh 2048Wh 2560Wh 2560Wh 3840Wh 5120Wh
*Discharge current ≤1C
CYCLE LIFE (capacity 80% of nominal)
80% DoD 2500 cycles
70% DoD 3000 cycles
50% DoD 5000 cycles
DISCHARGE
Maximum continuous
discharge current
120A 200A 300A 320A 400A 400A 600A 400A
Recommended continuous
discharge current
60A 100A 150A 160A 200A 200A 300A 200A
End of discharge voltage 11V 11V 11V 11V 11V 11V 11V 22V
OPERATING CONDITIONS
Operating temperature Discharge: -20°C to +50°C Charge: +5°C to +50°C
Storage temperature -45°C to +70°C
Humidity (non-condensing) Max. 95%
Protection class IP 22
CHARGE
Charge voltage Between 14V/28V and 14,4V/28,8V (14,2V/28,4V recommended)
Float voltage 13,5V/27V
Maximum charge current 120A 200A 300A 320A 400A 400A 600A 400A
Recommended charge
current
30A 50A 75A 80A 100A 100A 150A 100A
OTHER
Max storage time @ 25°C* 1 year
BMS connection Male + female cable with M8 circular connector, length 50cm
Power connection (threaded
inserts)
M8 M8 M8 M10 M10 M10 M10 M8
Dimensions (hxwxd) mm
240 x 285 x 132 197 x 321 x 152 237 x 321 x 152 320 x 338 x 233 297 x 425 x 274 237 x 321 x 152 347 x 425 x 274 317 x 631 x 208
Weight 12kg 15kg 20kg 33kg 42kg 22kg 51kg 56kg
*When fully charged