Product Card
Our LFP batteries have integrated cell balancing and cell monitoring. Up to 5 batteries can be paralleled and up to four batteries can be
series connected, so that a 48V battery bank of up to 1500Ah can be assembled. The cell balancing/monitoring cables can be daisy-
chained and must be connected to a Battery Management System (BMS).
Battery Management System (BMS)
The BMS will:
1. Disconnect or shut down the load whenever the voltage of a battery cell decreases to less than 2,5V.
2. Stop the charging process whenever the voltage of a battery cell increases to more than 4,2V.
3. Shut down the system whenever the temperature of a cell exceeds 50°C.
See the BMS datasheets for more features
Battery specification
VOLTAGE AND CAPACITY
LFP-
Smart
12,8/60
LFP-
Smart
12,8/100
LFP-
Smart
12,8/150
LFP-
Smart
12,8/160
LFP-
Smart
12,8/200
LFP-
Smart
12,8/200-a
LFP-
Smart
12,8/300
LFP-
Smart
25,6/200
Nominal voltage 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 25,6V
Nominal capacity @ 25°C*
60Ah 100Ah 150Ah 160Ah 200Ah 200Ah 300Ah 200Ah
Nominal capacity @ 0°C*
48Ah 80Ah 125Ah 130Ah 160Ah 160Ah 240Ah 160Ah
Nominal capacity @ -20°C* 30Ah 50Ah 75Ah 80Ah 100Ah 100Ah 150Ah 100Ah
Nominal energy @ 25°C* 768Wh 1280Wh 1920Wh 2048Wh 2560Wh 2560Wh 3840Wh 5120Wh
*Discharge current ≤1C
CYCLE LIFE (capacity ≥ 80% of nominal)
80% DoD 2500 cycles
70% DoD 3000 cycles
50% DoD 5000 cycles
DISCHARGE
Maximum continuous
discharge current
120A 200A 300A 320A 400A 400A 600A 400A
Recommended continuous
discharge current
≤60A ≤100A ≤150A ≤160A ≤200A ≤200A ≤300A ≤200A
End of discharge voltage 11V 11V 11V 11V 11V 11V 11V 22V
OPERATING CONDITIONS
Operating temperature Discharge: -20°C to +50°C Charge: +5°C to +50°C
Storage temperature -45°C to +70°C
Humidity (non-condensing) Max. 95%
Protection class IP 22
CHARGE
Charge voltage Between 14V/28V and 14,4V/28,8V (14,2V/28,4V recommended)
Float voltage 13,5V/27V
Maximum charge current 120A 200A 300A 320A 400A 400A 600A 400A
Recommended charge
current
≤30A ≤50A ≤75A ≤80A ≤100A ≤100A ≤150A ≤100A
OTHER
Max storage time @ 25°C* 1 year
BMS connection Male + female cable with M8 circular connector, length 50cm
Power connection (threaded
inserts)
M8 M8 M8 M10 M10 M10 M10 M8
Dimensions (hxwxd) mm
240 x 285 x 132 197 x 321 x 152 237 x 321 x 152 320 x 338 x 233 297 x 425 x 274 237 x 321 x 152 347 x 425 x 274 317 x 631 x 208
Weight 12kg 15kg 20kg 33kg 42kg 22kg 51kg 56kg
*When fully charged