Product Card
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands 
General phone: +31 (0)36 535 97 00 | E-mail: sales@victronenergy.com 
www.victronenergy.com 
Our LFP batteries have integrated cell balancing and cell monitoring. Up to 5 batteries can be paralleled and up to four 12V batteries or 
two 24V batteries can be series connected, so that a 48V battery bank of up to 1500Ah can be assembled. The cell balancing/monitoring 
cables can be daisy-chained and must be connected to a Battery Management System (BMS).  
Battery Management System (BMS) 
The BMS will: 
1.  Generate a pre-alarm whenever the voltage of a battery cell decreases to less than 3,1V (adjustable 2,85 - 3,15 V). 
2.  Disconnect or shut down the load whenever the voltage of a battery cell decreases to less than 2,8V (adjustable 2,6 V - 2,8 V). 
3.  Stop the charging process whenever the voltage of a battery cell increases to more than 3,75 V or the temperature increases to 
more than 60°C. 
See the BMS datasheets for more features 
Battery specification 
VOLTAGE AND CAPACITY 
LFP- 
Smart 
12,8/50 
LFP- 
Smart 
12,8/60 
LFP- 
Smart 
12,8/100 
LFP- 
Smart 
12,8/160 
LFP- 
Smart 
12,8/200 
LFP- 
Smart 
12,8/300 
LFP- Smart 
12,8/330 
LFP- Smart 
25,6/100 
LFP- 
Smart 
25,6/200 
LFP- 
Smart 
25,6/200-a 
Nominal voltage  12,8V  12,8V  12,8V  12,8V  12,8V  12,8V  12,8V  25,6V  25,6V  25,6V 
Nominal capacity @ 25°C* 
50Ah  60Ah  100Ah  160Ah  200Ah  300Ah  330Ah  100Ah  200Ah  200Ah 
Nominal capacity @ 0°C* 
40Ah  48Ah  80Ah  130Ah  160Ah  240Ah  260Ah  80Ah  160Ah  160Ah 
Nominal capacity @ -20°C*  25Ah  30Ah  50Ah  80Ah  100Ah  150Ah  160Ah  50Ah  100Ah  100Ah 
Nominal energy @ 25°C*  640Wh  768Wh  1280Wh  2048Wh  2560Wh  3840Wh  4220Wh  2560Wh  5120Wh  5120Wh 
*Discharge current ≤1C 
CYCLE LIFE (capacity ≥ 80% of nominal) 
80% DoD  2500 cycles 
70% DoD  3000 cycles 
50% DoD  5000 cycles 
DISCHARGE 
Maximum continuous 
discharge current 
100A  120A  200A  320A  400A  600A  400A  200A  400A  400A 
Recommended continuous 
discharge current 
≤50A  ≤60A  ≤100A  ≤160A  ≤200A  ≤300A  ≤300A  ≤100A  ≤200A  ≤200A 
End of discharge voltage  11,2V  11,2V  11,2V  11,2V  11,2V  11,2V  11,2V  22,4V  22,4V  22,4V 
OPERATING CONDITIONS 
Operating temperature  Discharge: -20°C to +50°C  Charge: +5°C to +50°C 
Storage temperature  -45°C to +70°C 
Humidity (non-condensing)  Max. 95% 
Protection class  IP 22 
CHARGE 
Charge voltage  Between 14V/28V and 14,4V/28,8V (14,2V/28,4V recommended) 
Float voltage  13,5V/27V 
Maximum charge current  100A  120A  200A  320A  400A  600A  400A  200A  400A  400A 
Recommended charge 
current 
≤30A  ≤30A  ≤50A  ≤80A  ≤100A  ≤150A  ≤150A  ≤50A  ≤100A  ≤100A 
OTHER 
Max storage time @ 25°C*  1 year 
BMS connection  Male + female cable with M8 circular connector, length 50cm 
Power connection 
(threaded inserts) 
M8  M8  M8  M8  M8  M10  M10  M8  M8  M8 
Dimensions (hxwxd) mm 
199 x 188 x 
147 
239 x 286 
x132 
197 x 321 x 
152 
237 x 321 x 
152 
237 x 321 x 
152 
347 x 425 x 
274 
265 x 359 x 
206 
197 x 650 x 
163 
317 x 631 
x 208 
237 x 650 x 
163 
Weight  7kg  12kg  14kg  18kg  20kg  51kg  30kg  28kg  56kg  39kg 
*When fully charged 