Product Card

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | E-mail: sales@victronenergy.com
www.victronenergy.com
Our LFP batteries have integrated cell balancing and cell monitoring. Up to 5 batteries can be paralleled and up to four 12V batteries or
two 24V batteries can be series connected, so that a 48V battery bank of up to 1500Ah can be assembled. The cell balancing/monitoring
cables can be daisy-chained and must be connected to a Battery Management System (BMS).
Battery Management System (BMS)
The BMS will:
1. Generate a pre-alarm whenever the voltage of a battery cell decreases to less than 3,1V (adjustable 2,85 - 3,15 V).
2. Disconnect or shut down the load whenever the voltage of a battery cell decreases to less than 2,8V (adjustable 2,6 V - 2,8 V).
3. Stop the charging process whenever the voltage of a battery cell increases to more than 3,75 V or the temperature increases to
more than 60°C.
See the BMS datasheets for more features
Battery specification
VOLTAGE AND CAPACITY
LFP-
Smart
12,8/50
LFP-
Smart
12,8/60
LFP-
Smart
12,8/100
LFP-
Smart
12,8/160
LFP-
Smart
12,8/200
LFP-
Smart
12,8/300
LFP- Smart
12,8/330
LFP- Smart
25,6/100
LFP-
Smart
25,6/200
LFP-
Smart
25,6/200-a
Nominal voltage 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 12,8V 25,6V 25,6V 25,6V
Nominal capacity @ 25°C*
50Ah 60Ah 100Ah 160Ah 200Ah 300Ah 330Ah 100Ah 200Ah 200Ah
Nominal capacity @ 0°C*
40Ah 48Ah 80Ah 130Ah 160Ah 240Ah 260Ah 80Ah 160Ah 160Ah
Nominal capacity @ -20°C* 25Ah 30Ah 50Ah 80Ah 100Ah 150Ah 160Ah 50Ah 100Ah 100Ah
Nominal energy @ 25°C* 640Wh 768Wh 1280Wh 2048Wh 2560Wh 3840Wh 4220Wh 2560Wh 5120Wh 5120Wh
*Discharge current ≤1C
CYCLE LIFE (capacity 80% of nominal)
80% DoD 2500 cycles
70% DoD 3000 cycles
50% DoD 5000 cycles
DISCHARGE
Maximum continuous
discharge current
100A 120A 200A 320A 400A 600A 400A 200A 400A 400A
Recommended continuous
discharge current
50A 60A 100A 160A 200A 300A 300A 100A 200A 200A
End of discharge voltage 11,2V 11,2V 11,2V 11,2V 11,2V 11,2V 11,2V 22,4V 22,4V 22,4V
OPERATING CONDITIONS
Operating temperature Discharge: -20°C to +50°C Charge: +5°C to +50°C
Storage temperature -45°C to +70°C
Humidity (non-condensing) Max. 95%
Protection class IP 22
CHARGE
Charge voltage Between 14V/28V and 14,4V/28,8V (14,2V/28,4V recommended)
Float voltage 13,5V/27V
Maximum charge current 100A 120A 200A 320A 400A 600A 400A 200A 400A 400A
Recommended charge
current
30A 30A 50A 80A 100A 150A 150A 50A 100A 100A
OTHER
Max storage time @ 25°C* 1 year
BMS connection Male + female cable with M8 circular connector, length 50cm
Power connection
(threaded inserts)
M8 M8 M8 M8 M8 M10 M10 M8 M8 M8
Dimensions (hxwxd) mm
239 x 286
x132
197 x 321 x
152
237 x 321 x
152
237 x 321 x
152
347 x 425 x
274
265 x 359 x
206
197 x 650 x
163
317 x 631
x 208
237 x 650 x
163
Weight 7kg 12kg 14kg 18kg 20kg 51kg 30kg 28kg 56kg 39kg
*When fully charged