Product Manual
Table Of Contents
- Lynx Smart BMS
- Table of Contents
- 1. Safety Precautions
- 2. Introduction
- 3. Features
- 4. Communication and interfacing
- 5. System Design
- 6. Installation
- 7. Commissioning the Lynx Smart BMS
- 8. Operation Lynx Smart BMS
- 9. Troubleshooting and Support
- 9.1. Lynx Smart BMS does not power up
- 9.2. Lynx Smart BMS operational issues
- 9.3. BMS issues
- 9.3.1. The BMS frequently disables the battery charger
- 9.3.2. The BMS is prematurely turning chargers off
- 9.3.3. The BMS is prematurely turning loads off
- 9.3.4. The pre-alarm setting is missing in VictronConnect
- 9.3.5. BMS is displaying alarm while all cell voltages are within range
- 9.3.6. How to test if the BMS is functional
- 9.3.7. System in sleep or hibernate mode
- 9.3.8. Battery communication error
- 9.4. Battery monitor issues
- 9.5. VictronConnect issues
- 9.6. GX device issues
- 10. Warranty
- 11. Technical specifications Lynx Smart BMS
- 12. Appendix
SoC cycle end
The state of charge cycle end setting is used to ......
This setting is fixed at 90%.
SoC cycle
The state of charge cycle setting is used to ......
This setting is fixed at 65%.
SoC full discharge
The state of charge full discharge setting is used to ......
This setting is fixed at 5%.
6.3.5. Settings Lynx Distributor
These instructions only apply if the system contains one or more Lynx Distributors.
Each Lynx distributor must be addressed and set to A, B, C or D. This is done via a 2-way dip switch located inside the Lynx
distributor. Refer to chapter 6.1.3. Addressing Lynx Distributor in the Lynx distributor manual.
Use the VictronConnect App to give each fuse a custom name (maximum 16 characters). If the fuse name is empty (0
characters), the fuse will be disabled from monitoring and be ignored.
• Navigate to the settings page by clicking the gear symbol at the top right-hand corner.
• On the settings page scroll down to the Lynx Distributor settings.
• Click on a fuse name and a window opens to rename the fuse.
Setting the Lynx Distributor fuse names using VictronConnect
Lynx Smart BMS
Page 24 Installation