Recovery sequence after low voltage shutdown
Below chart follows the stages the BMS goes through when the battery is charged. The chart starts when the battery has a low
cell voltage alarm and finishes when the battery has been recharged.
Stage 1 Stage 2 Stage 3
BMS state Operational Operational Operational
Battery stage Discharged Charging Charging
Battery cell voltages One or more battery cells
are below the 2.8V low cell
voltage threshold
The cell voltages are
increasing
All battery cells are above
3.2V
Alarms or warnings Under voltage alarm Under voltage alarm None
Contactor state Closed Closed Closed
LED
Green and 3 red flashes
every 4 seconds
Green and 3 red flashes
every 4 seconds
Green
DVCC (GX device) control
Reduced charge
No discharge
Reduced charge
No discharge
Full charge
Full discharge
ATC contact state Closed Closed Closed
ATD contact state Open Open Closed
Programable relay
Contact between COM and
NO (alarm)
Contact between COM and
NO (alarm)
Contact between COM and
NC (no alarm)
Voltage and current graph:
A. Battery voltage (blue)
B. Battery current
(orange)
Lynx Smart BMS