Product Manual

8
victron energy
Adjustments with remote panel Phoenix
Charger Control
WARNING: Always check with your battery
supplier if the choosen charge characteristic
is suitable for your battery and application
Remove the frontplate and connect the
Phoenix Charger Control panel to the 8-pin
modular jack.
Disconnect battery, Voltage sense and
Temperature sense. A voltmeter is not required
but may be useful.
While switching on keep one of the
pushbuttons & pushed.
Release pushbutton.
The adjust knob on the remote panel controls
the adjust-mode; the LED’s on the charger
correspond with the knob as follows:
knob adjust mode charger LED’s
0% not impl. Failure
10% Bulk Failure Bulk
20% Absorption Failure Absorption
30% Float Failure Float
40% Rep. Abs. interval Failure Abs./Float
50% Rep. Abs. time Failure Bulk/Abs.
60% Max. Abs. time Failure Bulk/Float
70% Characteristic Failure Bulk/Abs./Float
80% Battery type Failure/Abs. Float
90% not impl. Failure
100% not impl. Failure
Push for up and for down.
LED indicators on remote panel read the
value as follows:
LED flashing = 1 step
LED on = 2 steps
1 bar flashing = 9 steps
Left bar is [step x10], right bar is [step x1].
To read the Float and Absorption adjustment the
lowest value in the table has to be added:
12 V models 24V models
Bulk 0 – 50 A/30A;step 1A
0 – 25 A / 16 A; step 1 A
Abs
12.00 – 16.00 V;
step 0.1 V
24.00 – 32.00 V;
step 0.1 V
Float 12.00 – 16.00 V;
step 0.1 V
24.00 – 32.00 V;
step 0.1 V
Rep. Abs. int. 0 – 45 days; step 1 day ; def.= 7 days
Rep. Abs. time 0 – 72 qu. of an hour; step 1 qu.; def = 4 qu.
Max. Abs. time or
Fixed Abs. time
1 – 8 hrs ; default = 4 hrs.
Characteristic 1 = Fixed: Fixed Abs. time. default = 4 hrs.
Rep. Abs. int. default = 1 day
Rep. Abs. time. default = 2 qu.
2 = Adaptive
3 = Adaptive with BatterySafe mode (default)
Battery type
default = 1
Abs. Volt
age Float Voltage /
Reduced Float
Max.Abs. time
0: User defined
1: Sonnenschein
Dryfit A200 gel
14.4 V 28.8 V 13.8 V/
13.0 V
27.6 V/
26.0 V
4 hrs.
2: Traction
(tubular plate)
15.0 V 30.0 V 13.8 V/
13.0 V
27.6 V/
26.0 V
6 hrs.
3: Semitraction
1
14.4 V 28.8 V 14.0 V/
13.0 V
28.0 V/
26.0 V
5 hrs.
4: Victory
1
14.8 V 29.6 V 14.0 V/
13.0 V
28.0 V/
26.0 V
5 hrs.
12V
model
24V
model
12V
model
24V
model
Turn the knob to another adjust-mode to store or
switch Off to escape.
Switch Off and On to start normal charging
sequence.
Replace the frontplate.
Warning: If the knob is not turned after an
adjustment the charger will not store this
adjustment. If the Float or Absorption voltage
was adjusted and the charger is not switched off
this voltage will remain on the outputs.
1
The optimum absorption voltage of flat plate lead acid batteries depends on mechanical and chemical properties. Batteries with high antimony
doping can general be charged with a lower absorption voltage than batteries with low antimony doping, like the Victory carbon fibre battery.
(See the book "Electricity on board" at
www.victronenergy.com )
30
Float voltage =
12+(1x1)+(4x0.2)= 13.8 volts (12V model)
24+(1x1)+(4x0.2)= 25.8 volts (24V model)
50
Repeated Absorption time =
4 quarters of an hour
70
Characteristic =
1. Fixed mode
40
Repeated Absorption interval
= 7 days
20
Absorption voltage =
12+(1x2)+(2x0.2)= 14.4 volts (12V model)
24+(1x2)+(2x0.2)= 26.4 volts (24V model)
60
Maximum Absorption time =
4 hrs.
80
Battery type =
1. Gel
10
Max. Bulk current =
25 amps