Brochure

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40
E-mail: sales@victronenergy.com |
www.victronenergy.com
Phoenix Inverter 12/3000 24/3000
Parallel,3-phase and split-phase operation Yes
INVERTER
Input voltage range (V DC) 9,5 17V 19 33V
Output Output voltage: 120 VAC ±2% Frequency: 60 Hz ± 0,1% (1)
Cont. output power at 25ºC / 77ºF (VA) (2)
3000 3000
Cont. output power at 25ºC / 77ºF (W)
2400 2400
Cont. output power at 40ºC / 104ºF (W)
2200 2200
Cont. output power at 65ºC / 150ºF (W)
1700 1700
Peak power (W) 6000 6000
Max. efficiency (%) 93 94
Zero load power (W) 20 20
Zero load power in AES mode (W) 15 15
Zero load power in Search mode (W) 8 10
GENERAL
Programmable relay (3) Yes
Protection (4) a - g
VE.Bus communication port For parallel and three phase operation, remote monitoring and system integration
Remote on-off Yes
Common Characteristics
Operating temperature range: -40 to +65ºC (-40 - 150°F)
Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
Battery-connection 2+2 M8 bolts
230 V AC-connection Screw terminals
Weight 18 kg 38 lbs
Dimensions (hxwxd) 362x258x218 mm 14.3x10.2x8.6 inch
STANDARDS
Safety EN 60335-1
Emission Immunity EN 55014-1 / EN 55014-2
2) Non-linear load, crest factor 3:1
3) Programmable relay that can a.o. be set for
general alarm, DC under voltage or genset
start/stop function.
AC rating: 230 V/4A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
4) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 V AC on inverter output
g) input voltage ripple too high
Computer controlled operation and monitoring
Several interfaces are available:
This panel can also be used on a MultiPlus
inverter/charger when an automatic transfer
switch but no charger function is desired.
The brightness of the LEDs is automatically
reduced during night time.
BMV Battery Monitor
The BMV Battery Monitor features an
advanced microprocessor control system
combined with high resolution measuring
systems for battery voltage and charge /
discharge current. Besides this, the software
includes complex calculation algorithms, like
Peukert’s formula, to exactly determine the
state of charge of the battery. The BMV
selectively displays battery voltage, current,
consumed Ah or time to go. The monitor
also stores a host of data regarding
performance and use of the battery.
Several models available (see battery
monitor documentation).
Color Control GX
Provides monitor and control. Locally, and also
remotely on the VRM Portal.
MK3-USB VE.Bus to USB interface
Connects to a USB port (see ‘A guide to
VEConfigure’)
VE.Bus to NMEA 2000 interface
Connects the device to a NMEA2000 marine
electronics network. See the NMEA2000 & MFD
integration guide