Manual
7
EN NL FR DE ES Appendix
5. Technical data, continued
Phoenix Inverter
12 Volt
24 Volt
48 Volt
12/1200
24/1200
48/1200
Cont. power at 25°C (1)
1200 VA
Cont. power at 25°C / 40°C
1000 / 900 W
Peak power
2400 W
Output AC voltage / frequency (adjustable)
230 VAC or 120 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Input voltage range
9,2 - 17 / 18,4 - 34,0 / 36,8 - 62,0 VDC
Low battery shut down (adjustable)
9,3 / 18,6 / 37,2 VDC
Low battery restart & alarm (adjustable)
10,9 / 21,8 / 43,6 VDC
Battery charged detect (adjustable)
14,0 / 28,0 / 56,0 VDC
Max. efficiency
92 / 94 / 94 %
Zero-load power
8 / 9,5 / 10 W
Default zero-load power in ECO mode
(default search interval: 2,5 s, adjustable)
1 / 1,7 / 2,7 W
ECO mode stop and start power setting
Adjustable
Protection (2)
a – f
Operating temperature range
-40 to +60°C (fan assisted cooling)
(derate 1,25% per °C above 40°C)
Humidity (non-condensing)
max 95%
ENCLOSURE
Material & Colour
Steel chassis and plastic cover (blue Ral 5012)
Battery-connection
Screw terminals
Maximum cable cross-section
35/25/25mm² / AWG2/4/4
Standard AC outlets
230V: Schuko (CEE 7/4), IEC-320 (male plug included)
UK (BS 1363), AU/NZ (AS/NZS 3112)
120V: Nema5-15R
Protection category
IP 21
Weight
7,7 kg/17 lbs
Dimensions (hxwxd, mm)
(hxwxd, inch)
117x232x327
4,6x9,1x12,9
(12V model: 117x232x367)
ACCESSORIES
Remote on-off
Yes
Automatic transfer switch
Filax or Multi
STANDARDS
Safety
EN/IEC 60335-1 / EN/IEC 62109-1
EMC
EN 55014-1 / EN 55014-2
IEC 61000-6-1 / IEC 61000-6-3
Automotive Directive
ECE R10-4 EN 50498
1) Nonlinear load, crest factor 3:1
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) DC ripple too high