4.4.6 Three-phase operation (800VA and 1200VA models only, see appendix D)
The MultiPlus can also be used in 3-phase wye (Y) configuration. To this end, a connection
between the devices is made by means of standard RJ45 UTP cables and a splitter (the
same as for parallel operation). The system (MultiPlus units plus an optional control panel)
will require subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
Note: the MultiPlus is not suitable for 3-phase delta (Δ) configuration.
5. CONFIGURATION
Settings may only be changed by a qualified engineer
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
5.1 Standard settings: ready for use
On delivery, the Multi is set to standard factory values. In general, these settings are
suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your
batteries! Refer to the manufacturer's documentation or to your battery supplier!
Standard Multi factory settings
Inverter frequency 50 Hz
Input frequency range 45 - 65 Hz
Input voltage range 180 - 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
Search mode off
Ground relay on
Charger on/ off on
Battery charge algorithm four-stage adaptive with BatterySafe mode
Charge current 100% of the maximum charge current
Battery type Victron Gel Deep Discharge (also suitable
for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 14.4 / 28.8 / 57,6V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 13.8 / 27.6 / 55,2V
Storage voltage 13.2 / 26.4 / 52,8V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection off
AC input current limit 12A (= adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Programmable relay alarm function