Product Card

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
General phone: +31 (0)36 535 97 00 | E-mail: sales@victronenergy.com
www.victronenergy.com
Monitor and manage your Victron Energy system from
your smart phone and tablet. Available for both iOS and
Android.
VRM Portal
Our free remote monitoring website (VRM) will display all your
system data in a comprehensive graphical format. System settings
can be changed remotely via the portal. Alarms can be received
by e-mail.
Current sensor 100A:50mA
To implement PowerControl and PowerAssist and
to optimize self-consumption with external
current sensing.
Maximum current: 50A resp. 100A.
Length of connection cable: 1 m.
MultiPlus-II GX 24/3000/70-32 48/3000/35-32 48/5000/70-50
PowerControl & PowerAssist
Yes
Transfer switch
32A
50A
Maximum AC input current
32A
50A
Auxiliary output
Yes (32A)
INVERTER
DC Input voltage range
1933V
38 66V
Output
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C
(3)
3000VA
5000VA
Cont. output power at 25°C
2400W
4000W
Cont. output power at 40°C
2200W
3700W
Cont. output power at 65°C
1700W
3000W
Maximum apparent feed-in power
2500VA
4000VA
Peak power
5500W
9000W
Maximum efficiency
94%
95%
96%
Zero load power
13W
11W
18W
Zero load power in AES mode
9W
7W
12W
Zero load power in Search mode
3W
2W
2W
CHARGER
AC Input
Input voltage range: 187-265 VAC
Input frequency: 45 65 Hz
Charge voltage 'absorption'
28,8V
57,6V
Charge voltage 'float'
27,6V
55,2V
Storage mode
26,4V
52,8V
Maximum battery charge current (4)
70A
35A
70A
Battery temperature sensor
Yes
GENERAL
Interfaces
VE.Can, USB, Ethernet, VE.Direct, Wi-Fi
External AC current sensor (optional)
50A
100A
Programmable relay (
5)
Yes
Protection
(2)
a – g
VE.Bus communication port
For parallel and three phase operation,
remote monitoring and system integration
General purpose com. port
Yes, 2x
Remote on-off
Yes
Operating temperature range
-40 to +65°C (fan assisted cooling)
Humidity (non-condensing)
max 95%
ENCLOSURE
Material & Colour
Steel, blue RAL 5012
Protection category
IP22
Battery-connection
M8 bolts
230 V AC-connection
Screw terminals 13 mm² (6 AWG)
Weight
19 kg
30 kg
Dimensions (hxwxd) mm
506 x 275 x 147
565 x 323 x 148
STANDARDS
Safety
EN-IEC 60335-1, EN-IEC 60335-2-29,
EN-IEC 62109-1, EN-IEC 62109-2
Emission, Immunity
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Uninterruptible power supply
IEC 62040-1
Anti-islanding
Please consult the certificates on our website.
1) Can be adjusted to 60 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general alarm, DC
under voltage or genset start/stop function.
AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to
60VDC
Digital Multi Control Panel
A convenient and low-cost solution for remote
monitoring, with a rotary knob to set
PowerControl and PowerAssist levels.
Connection Area
GX GSM
A cellular modem; providing a mobile internet for the system
and connection to Victron Remote Management (VRM).
Optional: outdoor GSM antenna and GPS antenna.
For more detail please enter
GX GSM
in the search box on
our website