Only one remote control means (panel or switch) can be connected to the system. That means only one GX.
9.5.7 Three-phase operation
The product can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made
by means of standard RJ45 UTP cables (the same as for parallel operation). The system will require subsequent
configuration.
Pre-requisites: see Section Voltage Sense
1. Note: the product is not suitable for 3-phase delta (Δ) configuration.
2. When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allowed
in a three phase system.
For full details on parallel and three-phase configuration always discuss with your Victron distributor first and please see
this specific manual: https://www.victronenergy.com/live/ve.bus:manual_parallel_and_three_phase_systems
9.5.8 Connection to the VRM Portal
Connection of the product to VRM requires an internet connection. This can be made via wifi, or preferably a hardwired
ethernet cable to an internet connected router.
The VRM site id is located on a sticker inside the cable connections area of the device.
For more information to set up VRM, refer to the VRM Getting Started Manua
10. Configuration
This section is intended mainly for stand-alone applications
For grid connected Energy Storage Systems (ESS) please see https://www.victronenergy.com/live/ess:start
Settings may only be changed by a suitable qualified installer with the appropriate training, and subject to local
requirements. Please contact Victron for further information or necessary training.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
10.1 Standard settings: ready for use
On delivery, the product is set to standard factory values. In general, these settings are suitable for single-unit operation.
WARNING
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard factory settings
Setting
Value
Inverter frequency
50 Hz
Input frequency range
45 65 Hz
Input voltage range
180 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
AES (Automatic Economy Switch)
off
Ground relay
On
Charger on / off
on
Battery charge curve
four-stage adaptive with BatterySafe mode
Charging current
100% of the maximum charging current
Battery type
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
Discharge)
Automatic equalisation charging
off
Absorption voltage
57.6V
Absorption time
up to 8 hours (depending on bulk time)