Product Manual

17
EN NL FR DE ES SE IT Appendix
14. TECHNICAL SPECIFICATIONS
MultiPlus-II GX
Yes
INVERTER/CHARGER
PowerControl & PowerAssist
32A
Transfer switch
32A
Maximum AC input current
Yes (32A)
Auxiliary output
Yes
INVERTER
Input voltage range
38 66V
Output Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C (3) 3000VA / 2400W
Cont. output power at 40°C / 65°C 2200W / 1700W
Maximum apparent feed-in power 2500VA
Peak power
5500W
Maximum efficiency 95%
Zero load power 11W
Zero load power in AES mode 7 W
Zero load power in Search mode 2W
CHARGER
AC Input
Input voltage range: 187-265 VAC Input frequency: 45 65 Hz
Charge voltage 'absorption'
57,6V
Charge voltage 'float' 55,2V
Storage mode 52,8V
Maximum battery charge current (4) 35A
Battery temperature sensor
Yes
Programmable relay (5)
Yes
Protection (2) a - g
VE.Bus communication port For parallel and three phase operation, remote monitoring and system integration
General purpose com. port Yes, 2x
GENERAL
Interfaces VE.Can, USB, Ethernet, VE.Direct, Wi-Fi
Remote on-off Yes
Operating temp. range -40 to +65°C (fan assisted cooling)
Humidity (non-condensing): max 95%
ENCLOSURE
Material & Colour Steel, blue RAL 5012
Protection category IP21
Battery-connection M8 bolts
230 V AC-connection
Screw terminals 13 mm
2
(6 AWG)
Weight
26kg
Dimensions (hxwxd) 506 x 275 x 147 mm
STANDARDS
Safety
EN-IEC 60335-1, EN-IEC 60335-2-29
Emission / Immunity
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Anti-islanding See our website
1) Can be adjusted to 60 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function.
AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC