Product Manual

Manual Skylla with universal input 21
4.10 Connecting the output voltage alarm
The charger is equipped with a potential free alarm contact (change over type).
If the battery voltage is in between Vmin and Vmax the contact is activated.
(See figure 8, remote connections: NO, NC, COM).
Model
Vmin
Vmax
24V
23,8 Vdc
33,5 Vdc
4.11 Connecting remote panels
Victron Energy provides two optional remote panels that can be connected to the
charger. See illustration 8 for the circuit board connector where the remote panels
have to be connected to.
The COV panel:
The maximum charging current of 30A, 50A or 100A, according to the model, can
be limited with an external panel. This panel, the Victron Energy COV panel,
contains an adjustable potentiometer. Limiting the maximum charging current can
be useful to meet the batteries specifications, or to make sure the shore fuse
does not blow.
To connect the panel:
Disconnect the mains.
Connect the panel to the “+ pot” and “-pot” connector.
The CMV panel:
This panel indicates the charging mode and possible failures.
To connect the panel:
Disconnect the mains.
Connect the boost led to the “ L_BO” connector.
Connect the equalize led to the “L_EQ” connector.
Connect the float led to the “L_FL” connector.
Connect the failure led to the “L_FA” connector.
Connect the ground of the panel to the “GND” connector.
The CSV panel:
With the CSV panel the charger can be switched on or off. On the panel a green
“on” led is present. To operate the CSV panel you first have to switch the charger
on with the on/off switch located on the front panel of the charger.
To connect the panel:
Disconnect the mains
Connect the on led to the “L_ON” connector.
Connect the ground of the panel to the “GND” connector.
Connect the “TG switch” to the “REM” connector.