Product Manual
Manual Skylla with universal input 23
4.14 Connecting a voltmeter
The remote-connector offers a possibility to connect a voltmeter. It is possible to
connect a digital as well as an analogue voltmeter. This output can only be used
when the voltage-sense is connected. The voltage at this output is equal to the
voltage measured at the point where the voltage sense wires are connected.
Connecting a voltmeter
Disconnect the mains voltage.
Make sure that the voltage sense wires are connected, see chapter 4.8.
Connect a black wire between the “-” connection of the voltmeter and “-VM” at
the remote connector.
Connect a red wire between the “+” connection of the voltmeter and “+VM” at
the remote connector.
Connect the mains voltage.
4.15 Connecting a ampèremeter
The remote connector offers a possibility to connect an ampèremeter, which
indicates the output current of the charger. For the 30A charger an ampèremeter,
which indicates 30A at 60mV input voltage is required. For the 50A charger an
ampèremeter, which indicates 50A at 60mV input voltage is required, likewise for
the 100A charger an ampèremeter, which indicates 100A at 60mV input voltage is
required.
Connecting an ampèremeter
Disconnect the mains voltage.
Connect a black wire between the “-” connection of the ampèremeter and “-
AM” at the remote connector.
Connect a red wire between the “+” connection of the ampèremeter and “+AM”
at the remote connector.
Connect the mains voltage.