12.4.8 Fire Advisory Profile
The fire advisory profile is used with fire detection systems. You use it to send alarm messages to all
transmission destinations when an advisory fire detection device (such as an OSID Imager) detects fire. The
profile sends messages in both armed and disarmed states. It sends the alarm message again every
15 minutes as long as the alarm is active. When the system detects the end of alarm, it does not send a
new message indicating that the alarm is no longer active. Note that you cannot switch off the repeat alarm.
The profile type is 2 Fire advisory. Note that you cannot modify the profile type of the standard alarm
profiles.
12.4.9 Fire Verification Profile
The fire verification profile is used with fire detection systems. You use it to send alarm messages to all
transmission destinations when SmokeTrace has verified the presence of smoke. The profile sends
messages in both armed and disarmed states. It sends the alarm message again every 15 minutes as long