IM-PP 724607 0320 ProPress
Tube Diameter
(inches)
A minimum
(inches)
A minimum
(mm)
B minimum
(inches)
B minimum
(mm)
½ ¾ 19 1⅝ 41
¾ 22 2⅛ 54
1 1 26 64
1⅛ 29 2⅞ 73
45 89
2 2 51 4⅜ 111
Table 3: ProPress standard jaws clearance requirements
Tube
Diameter
(inches)
A
minimum
(inches)
A
minimum
(mm)
B
minimum
(inches)
B
minimum
(mm)
C
minimum
(inches)
C
minimum
(mm)
½ 23 1 ⅜ 35 2 ½ 64
¾ 1 26 1 ½ 38 2 ½ 64
1 1 ⅛ 29 1 ¾ 45 3 76
1 ¼ 1 ¼ 32 2 ¼ 57 3 ⅛ 80
1 ½ 1 ⅞ 48 2 ½ 64 3 ¾ 95
2 2 ⅛ 54 3 ⅛ 80 5 127
Table 4: ProPress standard jaws clearance requirements between tube, wall, and 󶈶oor
Tube Diameter
(inches)
A minimum
(inches)
A minimum
(mm)
B minimum
(inches)
B minimum
(mm)
½ ¾ 19 2 51
¾
22 2⅜ 60
1 26 2⅝ 67
1⅛ 28 3⅛ 85
Table 5: ProPress compact jaws clearance requirements
Tube
Diameter
(inches)
A
minimum
(inches)
A
minimum
(mm)
B
minimum
(inches)
B
minimum
(mm)
C
minimum
(inches)
C
minimum
(mm)
½ 23 1⅜ 35 64
¾ 1 26 38 70
1 1⅛ 29 1⅝ 41 3 76
1⅝ 39 2⅛ 53 3⅜ 85
Table 6: ProPress compact jaws clearance requirements between tube, wall, and 󶈶oor
A
B
A
B
C
20°
A
B
A
B
C
20°