Instructions / Assembly

Viega LLC
585 Interlocken Blvd.
Broomfield, CO 80021
Phone (800) 976-9819
www.viega.us
Product Instructions
Viega ProPress
®
½" to 2" Fittings
PI-PP 514822 0220 ProPress ½ to 2 (EN ES FR)
6
1
7 8
32
9
4
10
5 6
EN
Viega ProPress ½" to 2" Fittings
For Hard Copper Tubing in ½" to 2" and Soft
Copper Tubing in ½" to 1¼".
ProPress Insertion Depth Chart
Tube Size ½" ¾" 1" 1¼" 1½" 2"
Insertion Depth ¾" ⅞" ⅞" 1" 1
7
/
16
" 1
9
/
16
"
Viega products are designed to be
installed by licensed and trained plumbing
and mechanical professionals who are
familiar with Viega products and their installation.
Installation by non-professionals may void
Viega LLC’s warranty.
For applications requiring Viega ProPress
with FKM or HNBR sealing elements,
remove the factory-installed EPDM sealing
element and replace with an FKM or HNBR sealing
element. See Changing Sealing Elements Product
Instructions.
1
Cut the tube square using a displacement-type
cutter or fine toothed saw.
Note: Cut tubing a minimum of four inches away
from the contact area of the vise to prevent
possible damage to the tubing in the press area.
2
Deburr inside and outside of the tube to the
proper insertion depths to prevent cutting sealing
element.
DANGER!
Read and understand all instructions for
installing Viega ProPress fittings. Failure
to follow all instructions may result in extensive
property damage, serious injury, or death.
3
Check the sealing element for correct fit. Do not
use oils or lubricants. Use only Viega sealing
elements.
4
Mark the proper insertion depth as indicated by the
ProPress Insertion Depth Chart. Improper insertion
depth may result in an improper seal.
EN
Product Instructions
Viega ProPress
®
½" to 2"
This document is subject to updates. For the most current
Viega technical literature please visit www.viega.us.
5
While turning slightly, slide press fitting onto tubing to
the marked depth. End of tubing must contact stop.
6
Insert appropriate Viega ProPress jaw into the
press tool and push in, holding pin until it locks in
place.
7
Open the jaw and place at right angle on the
fitting. Visually check insertion depth using mark
on tubing.
8
Hold trigger on press tool until press jaws have
fully engaged the fitting. Jaws will automatically
release after a full press is made.
9
After pressing, open the jaw and remove the press
tool.
10
Pressure testing with Smart Connect
®
:
Unpressed connections are located by
pressurizing the system with air or water. When
testing with water the proper pressure range is
15 psi to 85 psi. When testing with compressed
air the proper pressure range is ½ psi to 45 psi
maximum. If testing with compressed air, use
an approved leak-detect solution. Following a
successful pressure test, the system may be
pressure tested up to 200 psi with air or up to 600
psi with water.
Testing for unpressed connections using
Smart Connect is not a replacement for
pressure testing requirements of local
codes and standards.
Warning!
Keep extremities and foreign objects away
from press tool during pressing operation
to prevent injury or incomplete press.
Copper tubing must be free of surface
imperfections, including metal stamped print
lines, before a ProPress fitting is installed.
ES
Instrucciones del producto
Viega ProPress
®
½" a 2"
Este documento está sujeto a actualizaciones. Para obtener la
documentación técnica más reciente de Viega, visite
www.viega.us.
FR
Instructions produit
ProPress
®
de Viega ½" à 2"
Le présent document est soumis à des mises à jour. Pour
consulter les manuels techniques Viega les plus récents,
veuillez visiter www.viega.us.