PEX Installation Manual
Table Of Contents
- 1 Introduction
- 2 Codes, Standards and Certifications
- 3 Viega PEX Installation Methods
- 4 Viega Manifolds
- 5 Viega PEX Press Fittings
- 6 Viega PEX Crimp Fittings
- 7 ViegaPEX Ultra Tubing
- 8 Viega FostaPEX Tubing
- 9 Viega PEX System Design and Sizing
- 10 System Sizing and Calculations
- 11 Water Service Installation
- 12 Installing the ManaBloc
- 13 Mounting the ManaBloc
- 14 Installing Manifold Distribution Lines
- 15 Installing the ViegaPEX Ultra Tubing System
- 16 Fastening the Viega PEX System
- 17 Installing Viega PEX Fittings
- 18 Pressure Testing Viega PEX Systems
- 19 System Disinfection
- 20 Warranty
IM-PF 724596 0416
50
Corner Expansion Offset (L, in)
per 50 linear feet of run
Tubing
∆T(°F)
Tube
nom.
60 80 100 120 140 160 180 200
ViegaPEX
&
ViegaPEX
Ultra
¾" 20.4 23.6 26.4 28.9 31.2 33.4 35.4 37.3
1" 23.2 26.7 29.9 32.8 35.4 37.8 40.1 42.3
1¼" 25.6 29.6 33.1 36.2 39.1 41.8 44.4 46.8
1½" 27.8 32.1 35.9 39.4 42.5 45.5 48.2 50.8
2" 31.8 36.8 41.1 45.0 48.6 52.0 55.1 58.1
Corner expansion offset:
Where piping takes a corner after a long straight run, a simple 90° elbow in the piping will allow for the
absorption of expansion.
Calculate the necessary “L” dimension between elbow and nearest fastener or use the chart below,
which was gured using the maximum run for a single expansion compensator (50 feet).
Following the previous example:
L = C√OD x ∆L
Where:
C = 12
OD = 1.125 (1" PEX)
∆L = 2.64"
L = 12√1.125" x 2.64" = 20.7"
L = 20.7"
Compensation distance:
To calculate the dimensions of the expansion compensation offset needed, use the following formula:
L = C√OD x ∆L
Where:
L = length of compensation distance
C = 12 (PEX material specic constant)
OD = outer tubing diameter (⅛" + nominal tube size)
∆L = change in length from temperature change
L = 20.7"
Illustration of Example
Figure 16.1 Corner Expansion
Table 16.2 Corner Expansion
Anchor Point
Anchor Point
Corner Offset
L
LT
∆L