PEX Installation Manual

Table Of Contents
IM-PF 724596 0416
52
U-Type Expansion Offset (in)
per 50 linear feet of run
Tubing
∆T(°F)
Tube
nom.
60 80 100 120 140 160 180 200
L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4
ViegaPEX
&
ViegaPEX
Ultra
¾" 4.1 8.2 4.7 9.4 5.3 10.5 5.8 11.6 6.2 12.5 6.7 13.3 7.0 14.2 7.5 14.9
1" 4.6 9.3 5.3 10.7 6.0 12.0 6.6 13.1 7.1 14.2 7.6 15.1 8.0 16.0 8.5 16.9
1¼" 5.1 10.2 5.9 11.8 6.6 13.2 7.2 14.5 7.8 15.6 8.4 16.7 8.9 17.7 9.4 18.7
1½" 5.6 11.1 6.4 12.9 7.2 14.4 7.9 15.7 8.5 17.0 9.1 18.2 9.6 19.3 10.2 20.3
2" 6.4 12.7 7.4 14.7 8.2 16.4 9.0 18.0 9.7 19.5 10.4 20.8 11.0 22.1 11.6 23.2
U-type expansion offset:
The U-type expansion loop integrates four 90° elbows that form a “U” pattern.
With this arrangement of the “L” dimension is applied as the width (represented as L3) while of “L” is
applied as each leg in the other dimension (represented as L4).
Calculate the necessary L3 and L4 dimensions or use the chart below, which was gured using the
maximum run for a single expansion compensator (50 feet).
L = 20.7"
L3 = (L)
L3 = 20.7"/5 = 4.14"
L3 = 4.14"
L4 = (L)
L4 = 2(20.7")/5 = 8.28"
L4 = 8.28"
The fastener shown on the L3 leg may be required to provide additional support depending on how the expansion loop is installed
(horizontal/vertical).
Illustration of Example
L4 = 8.28"
L3 = 4.14"
L4 = 8.28"
Figure 16.3 U-Type Expansion
Table 16.4 U-Type Expansion
Looped Offset
Anchor Point Anchor Point
L3
L4L4
4 - 6" 4 - 6"
L/2 L/2
LT