Technical information
3
5517 914 - 01
Vitorond 100 Direct Vent Systems Installation
In addition to the following instructions, also 
consult Field Controls Direct Vent System manual 
for detailed instructions on how to install the 
venting system.
Refer to Vitorond 100 Installation and Service
Instructions.
IMPORTANT
Do not install the regular galvanized vent pipe adaptor 
shipped with the boiler. This galvanized vent pipe adaptor 
is intended for chimney venting application and therefore 
must be discarded in a direct vent application.
Use a 4” to 3” reducer (not supplied) to connect an intake 
pipe to the Riello burner.
If no air intake is required a=0 then provide combustion 
air supply to mechanical room where the burner is installed. 
The burner requires fresh air for safe operation and must be 
installed in a mechanical room where there are provisions 
for adequate combustion and ventilation air.
Avoid dips in the venting system when using the flexible 
insulated stainless steel oil vent. The direct vent kit 
includes a VRV-4 vacuum relief valve which must be
installed in the air intake pipe as close as possible to the 
burner when using a Beckett burner.
*The direct vent kit includes a Viessmann-specific 
 stainless steel boiler-to-vent transition adaptor.
Installation
Installation of Insulated Stainless Steel Flexible Oil Vent








