Flue gas temperature sensor, Part No. 7450 630 Accessory
See page 48 for CM2 flue gas
temperature switch.
The sensor measures the flue gas
temperature and monitors the
selected limit value.
Electrical connection
The sensor is inserted in socket
”15” on the boiler control.
Check flue gas temperature sensor
1. Disconnect plug aG in the
terminal compartment of the
boiler control.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
Flue gas
temperature
in °C / °F
Resistance
in
180 / 176
160 / 320
200 / 392
650
800
880
3. Compare the value measured
with the actual temperature. If
the value differs significantly,
check installation and, if
necessary, replace sensor.
Technical data
Degree of
protection: IP 60
Ambient temperature
during operation:
–20 to + 600°C
3
2 to + 1112°F
during storage and transport:
–20 to + 70°C
–4 to + 158°F