Versatronik® 505 & 505D Communication Gateway BACnet IP Document Applicable to: Communication Versatronik 505 NR2/BACIP P/N 704050 Versatronik 505D NR2/BACIP P/N 704069 Applicable Controls Vitocontrol-S, MW1 and MW2 Vitotronic 300-K, MW1B and MW2B Vitotronic 100, GC1/GC1B Vitotronic 300, GW2 Vitotronic 300, GW5B Vitotronic 200, HO1 Vitodens 200 B2HA Technical, Installation and Configuration Information Cautionary Statement The information presented in this document is only to be used by those familiar wi
About these instructions ! Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION” and “IMPORTANT”. See below. ! WARNING KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
Important Regulatory and Installation Requirements Codes The installation of this unit must be in accordance with local codes. KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice All electrical wiring is to be done in accordance with the latest edition of CSA C22,1 Part 1 and/ or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70.
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Installation Mounting Versatronik Gateway—120VAC Unit KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice 2 1 4 1 3 Mounting Steps 1. Mount Versatronik 505 Gateway in a convenient location near the connected boiler controls control. Remove cover by loosening the two screws on either side of base to release the cover. 2. Fasten base to wall using field-supplied screws/fasteners. 3.
Installation Mounting Versatronik Gateway—24VAC DIN Rail Unit Mounting Steps 1 2 1. 2. 3. 4.
Versatronik 505 Dial Setting Overview Rotary Dial Setting Setting Overview 1. The rotary dial setting on the Versatronik Gateways provides addressing information for systems that may utilize a number of Versatronik Gateways. + #$ % + It is not required to make adjustments to the rotary dial setting. It should be left in the factory default position setting of 0.
Connection Overview—120VAC Communication connections—Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B BACnet IP Connection Overview Refer to manual specific to boiler control. Ensure necessary LON communication card installed. 1 Control showing location of LON card and its location within. 2 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway. 3 Versatronik 505 gateway.
Connection Overview—24VAC Communication connections—Vitotronic 100, GC1/GC1B, 300 GW2 or 300 GW5B BACnet IP Connection Overview Refer to manual specific to boiler/system control. Ensure necessary LON communication card installed. 1 Control showing location of LON card and its location within. 2 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway. 4 3 Versatronik 505 gateway.
Connection Overview—120VAC Communication connections—Vitocontrol-S, CT3/VD2A or Vitotronic 300-K MW1B BACnet IP Connection Overview BACnetIP RJ45 Connection Refer to manual specific to boiler/ system control. Ensure necessary LON communication card installed. 1 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway. Vitocontrol-S will need LON card installed.
Connection Overview—24VAC Communication connections—Vitocontrol-S, CT3/VD2A or Vitotronic 300-K MW1B BACnet IP " ! ! 2 Versatronik 505 gateway. " # ! 3 The RJ45 BACnetIP communication connection plugged into Versatronik 505 gateway. 4 Field-supplied 24VAC power supply for gateway. 1 A 3’/91cm CAT-5 cable is supplied with the gateway.
Connection Overview—120VAC Communication connections—Vitocontrol-S, MW2 for Vitodens 200, WB2B or Vitotronic 300-K, MW2B BACnet IP Connection Overview BACnetIP RJ45 Connection Refer to manual specific to boiler control. Ensure necessary LON communication card installed. 1 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway.
Connection Overview—120VAC Communication connections—Vitocontrol-S, MW2 for Vitodens 200, WB2B or Vitotronic 300-K, MW2B BACnet IP Refer to manual specific to boiler control. Ensure necessary LON communication card installed. " ! 1 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway.
Connection Overview—120VAC Communication connections—Vitodens 200, WB2B, HO1 and B2HA BACnet IP Connection Overview BACnetIP RJ45 Connection Refer to manual specific to boiler control. Ensure necessary LON communication card installed. 3 + #$ 2 Versatronik 505 gateway.
Connection Overview—24VAC Communication connections—Vitodens 200, WB2B, HO1 and B2HA BACnet IP Connection Overview " ! ! " 2 Versatronik 505 gateway. 2 # 1 A 3’/91cm CAT-5 cable is supplied with the gateway. The RJ45 is plugged into the control and terminates into the RJ45 socket inside of the Versatronik 505 gateway.
Update Participant List for Vitocontrol-S, Cascade Control Participant Update KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice This is to be carried out after all the communication connections have been completed and the Vitocontrol-S, is coded as the error manager. Requirements: Vitocontrol-S, must be coded as the error manager (default). Refer to the Vitocontrol-S manual address 79:01.
Participant Check Vitocontrol-S, Cascade Control Participant Check KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Service Diagnosis Actuator Coding Level 1 Fault History Service Functions Terminate Service? OK The participant check is used to confirm communication between the boiler controls and the Vitocontrol-S, system control. Requirements: Vitocontrol-S, must be coded as the error manager (default).
Configuration of Gateway KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Configuring BACnet/IP Settings Connect your computer DIRECTLY to the BACnet interface of the gateway device. With no other devices attached (an isolated network). Either set your computer’s network connection to automatic IP Address (DHCP), or set your computer’s IP address to 192.168.88.90 (subnet mask 255.255.255.0).
Configuration of Gateway Continued KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice BACnet Device Settings You can now reconfigure these settings according to your network requirements. Make sure that you press SAVE on every screen where you made changes. The new setting will not take effect until the Activate Configuration screen has been confirmed. These configuration pages can now be accessed through both the 192.168.88.
Configuration of Gateway Continued BACnet IP KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Analog Input Overview Point AI1 Point Description Unit Boiler 1 actual temperature °C/°F Vitotronic 300-K, MW2** Vitotronic 300, GW2 Vitotronic 200, HO1 **Vitodens boilers which communicate via KMK to the 300-K MW2B may not provide some points of information that LON communication does. Boiler/burner faults do not appear directly from the boiler. It is necessary to pick up the burner/boiler fault from the Cascade Fault Status.
Analog Input Overview Continued Point Point Description Unit Vitotronic 300-K, MW2 Vitotronic 333/300-K MW1 Vitotronic 300, GW2 Vitotronic 200, HO1 Vitotronic 100, GC1 KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Note: Temperature values only possible with specific installed sensors based on particular installation.
Analog Outputs Overview Point Vitotronic 300-K, MW2 Vitotronic 333/300-K MW1 Vitotronic 300, GW2 Vitotronic 200, HO1 Vitotronic 100, GC1 KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Note: Temperature values only possible with specific installed sensors based on particular installation.
Fault Codes Appendix A—Fault Codes Error codes for Viessmann control units based on controls/equipment installed KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Fault Codes Continued KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Additional Alarm/Fault Information KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice Viessmann controls show fault codes in hexadecimal format to conserve screen space on the user interface of the boiler and system controls. The Versatronik 505 gateway uses a SNVT_count variable which is usually displayed in decimal format. The base-format in which this fault can be displayed depends on your BMS software.
Status Information 2 Vitotronic 050/200H HK1M Vitotronic 050 HK1 Panel Vitotronic 050 HK3 Panel Vitotronic 300-K, MW1B, MW2B Vitotronic 200, HO1/Vitodens B2HA bit 21 : Re-circulation pump Vitotronic 333/300-K MW1 1 Vitotronic 300, GW2/GW5B Bit Relay State 0 bit 20 : DHW tank loading pump Vitotronic 100, GC1/GC1B KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Technical Information—120VAC 3 7 8 + + #$ 9 % % ) ( ( ( * ( 6 & & F1' 160mA & KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
Technical Information 4 6 7 " ! # ! " KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice KWE Technologies Group 750 McMurray Road Waterloo, Ontario, Canada N2V 2G5 Tel: (519) 747-5042 Fax: (519) 747-4448 www.kwe-tech.com info@kwe-tech.