Technical information
15
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice
Connection Overview—24VAC
Communication connections—Vitodens 200, WB2B, HO1 and B2HA
BACnet IP
!
"
!
#
"
!
24VAC
BACnetIP RJ45
BMS
Connection
4
Refer to manual specific to
boiler control. Ensure necessary
LON communication card
installed.
1 A 3’/91cm CAT-5 cable is
supplied with the gateway.
The RJ45 is plugged into the
control and terminates into
the RJ45 socket inside of the
Versatronik 505 gateway.
2 Versatronik 505 gateway.
3 The RJ45 BACnetIP
communication connection
plugged into Versatronik 505
gateway.
4 Field-supplied 24VAC power
supply for Versatronik
gateway.
5 Refer to boiler manual with
respect to installing LON
communications card inside
of boiler control.
Connection Overview
5
1
2
3