Technical information

20
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice
Configuration of Analog Outputs AO2-AO7
Configuration of Gateway Continued BACnet IP
Note: Status Light Operation
Flashing=communication
ON Solid or Off=no communication
Analog Output
Configuration Settings
System Examples AO2 AO3 AO4 AO5 AO6 AO7
Single Vitotronic 100, GC1/GC1B Boiler Control 1 0 0 0 1 0
Vitotronic 200, HO1 (Vitodens 200, WB2B) 1 0 0 0 201 2
Vitotronic 300, GW2 with 2 Mixing Valves 1 0 0 0 1 3
Vitotronic 300-K, with 2 Vitotronic 100, GC1 (high temp & 1 MV) 1 2 0 0 5 2
Vitotronic 300-K, with 4 Vitotronic 100, GC1 (high temp & 2 MV) 1 2 3 4 5 3
Vitotronic 300-K (Vitodens 200, WB2B/B2HA) Boiler KMK Comm. 0 0 0 0 205 3
Vitotronic 050/200-H, HK1 Mixing Valve Control 0 0 0 0 10 1
Vitotronic 050/200-H, HK3 Mixing Valve Control 0 0 0 0 10 3
Vitodens 200 B2HA 1 0 0 0 201 1
Vitotronic 300, GW5B with 2 Mixing Valves 1 0 0 0 1 3
Note: Analog output AO7 is a function of AO6. The AO7 setting determines the number of heating
circuits of the AO6 control.
The AO2 through to AO6 settings are based on the programmed participant number at address 77 of
the boiler controls.
Analog Output Overview Description
Point Point Description Details
AO1 Unit settings 0 = °C, 1 = °F
AO2 Boiler 1 LON Address* Participant # / Node ID (Address 77)
Default 1 -4 for Vitotronic 100 controls
Rotary Dial Position for KK10LON and KW10B
Add 100 (101 - 104) for KK10LON control
Add 200 (201 - 204) for KW10B control
AO3 Boiler 2 LON Address*
AO4 Boiler 3 LON Address*
AO5 Boiler 4 LON Address*
AO6 Zone/Cascade/Boiler LON
Address
Participant # of cascade/zone control
Default 5 for Vitotronic 300 control
Add 200 (205) for MW2 control (for use with WB2B
boiler over KMK-BUS)
AO7 Number of Zones on the Zone/
Cascade/Boiler
Number of zones on the cascade/zone control. Including
the common supply zone (A1). Set 0 if no cascade or 1
through 3 for number of zones.
*If Vitodens communicate via KMK communications with 300-K MW2B cascade control, the value that
will need to be entered is 0. Only LON communications with boiler require a LON address. See
example below