Technical information

22
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice
Point Point Description Unit
AI35 Zone/Cascade/Boiler Zone A1 Curve Room Temp. Normal °C/°F N Y Y Y Y Y
AI36 Zone/Cascade/Boiler Zone A1 Curve Room Temp. Reduce °C/°F N Y Y Y Y Y
AI37 Zone/Cascade/Boiler Zone M2 Supply Set-Point °C/°F N Y Y Y Y Y
AI38 Zone/Cascade/Boiler Zone M2 Supply Actual Temperature °C/°F N Y Y Y Y Y
AI39 Zone/Cascade/Boiler Zone M2 Curve Shift °K N Y Y Y Y Y
AI40 Zone/Cascade/Boiler Zone M2 Curve Slope N/A N Y Y Y Y Y
AI41 Zone/Cascade/Boiler Zone M2 Curve Room Temp. Normal °C/°F N Y Y Y Y Y
AI42 Zone/Cascade/Boiler Zone M2 Curve Room Temp. Reduce °C/°F N Y Y Y Y Y
AI43 Zone/Cascade/Boiler Zone M3 Supply Set-Point °C/°F N N N Y Y Y
AI44 Zone/Cascade/Boiler Zone M3 Supply Actual Temperature °C/°F N N N Y Y Y
AI45 Zone/Cascade/Boiler Zone M3 Curve Shift °K N N N Y Y Y
AI46 Zone/Cascade/Boiler Zone M3 Curve Slope N/A N N N Y Y Y
AI47 Zone/Cascade/Boiler Zone M3 Curve Room Temp. Normal °C/°F N N N Y Y Y
AI48 Zone/Cascade/Boiler Zone M3 Curve Room Temp. Reduce °C/°F N N N Y Y Y
Points Available Y/N
Analog Inputs Continued
Values which can be read from the Versatronik 505 NR2/BACIP Gateway
Analog Input Overview Continued
Point Point Description Unit
MI1 Boiler 1 Burner State *See table below
MI2 Boiler 2 Burner State *See table below
MI3 Boiler 3 Burner State *See table below
MI4 Boiler 4 Burner Stage *See table below
1 Off 5
2 Fault 6
3 10% 7
4 20% 8
30% 9 70%
40% 10 80%
50% 11 90%
60% 12 100%
State Value State Value State Value
Note: The burner percentage is only a control approximation and does not reflect the actual position.
Consult with burner manual or manufacturer for signal output from burner
Multi-state Burner Information—All Boiler Controls
Vitotronic 100, GC1
Vitodens 200, B2HA
Vitotronic 200, HO1
Vitotronic 300, GW2
Vitotronic 333/300-K MW1
Vitotronic 300-K, MW2
Note:
Temperature values only possible with specific
installed sensors based on particular installation.