Technical information
27
KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice
Appendix B—Status Information
x = always available for this device
k = dependent on configuration of device
n = not available for this device
Status Information
Bit Relay State
0 bit 2
0
: DHW tank loading pump k k k n k k k k
1 bit 2
1
: Re-circulation pump n k k n k k k k
2 bit 2
2
: Heating circuit pump 1 n k k x x k k x
3 bit 2
3
: Heating circuit pump 2 n k k n n k k k
4 bit 2
4
: Heating circuit pump 3 n k k n n k k n
5 bit 2
5
: Night-time contact HKP 1 n k k x x k k x
6 bit 2
6
: Night-time contact HKP 2 n k k n n k k k
7 bit 2
7
: Night-time contact HKP 3 n k k n n k k n
8 bit 2
8
: Supply pump n n n k k k n n
9 bit 2
9
: Primary pump heat exchanger set for DHW tank loading k k k n k k k n
bit 2
9
: DHW tank pump n n n n n n n k
10 bit 2
10
: Boiler circuit and distribution (common supply) pump k k k n n n n k
bit 2
10
: Internal Pump n n n n n n k x
11 bit 2
11
: Shunt pump k k k n n n n n
bit 2
11
: Diverting valve in space heating position n n n n n n n k
12 bit 2
12
: Flue gas heat exchanger pump x n n n n n n n
13 bit 2
13
: ThermControl switching contact k n n n n n n n
bit 2
13
: Diverting valve in DHW position n n n n n n n k
14 bit 2
14
: Burner 1
st
stage x x n n n n n n
15 bit 2
15
: Burner fault x x n n n n n n
bit 2
15
: Compiled fault n n n n n n n x
Vitotronic 100, GC1/GC1B
Vitotronic 300, GW2/GW5B
Vitotronic 333/300-K MW1
Vitotronic 050/200H HK1M
Vitotronic 050 HK3 Panel
Vitotronic 300-K, MW1B, MW2B
Vitotronic 200, HO1/Vitodens B2HA
Vitotronic 050 HK1 Panel