Operating instructions

116
Dis-
played
fault
code
Const. Weath.-
comp.
System char-
acteristics
Cause Measures
A7 X Control mode
as per deliv-
ered condition
Programming
unit faulty
Replace program-
ming unit
b0 X X Burner blocked Short circuit,
flue gas tem-
perature sen-
sor
Check flue gas
temperature sen-
sor
b1 X X Control mode
as per deliv-
ered condition
Communica-
tion fault, pro-
gramming
unit
Check connections
and replace pro-
gramming unit if re-
quired
b5 X X Control mode
as per deliv-
ered condition
Internal fault Replace the control
unit
b7 X X Burner blocked Boiler coding
card faulty
Plug in boiler cod-
ing card or replace
if faulty
b8 X X Burner blocked Lead break,
flue gas tem-
perature sen-
sor
Check flue gas
temperature sen-
sor
bA X Mixer regulates
to 20 °C flow
temperature.
Communica-
tion error, ex-
tension kit for
heating circuit 2
(with mixer)
Check extension
kit connections and
code.
bb X Mixer regulates
to 20 °C flow
temperature.
Communica-
tion error, ex-
tension kit for
heating circuit 3
(with mixer)
Check extension
kit connections and
code.
Troubleshooting
Fault codes
(cont.)
5772 909 GB