Operating instructions

118
Dis-
played
fault
code
Const. Weath.-
comp.
System char-
acteristics
Cause Measures
bE X Control mode
without remote
control
Communica-
tion error, re-
mote control
Vitotrol
heating circuit 3
(with mixer)
Check connec-
tions, cable, coding
address "A0" in
group "Heating
circuit" and re-
mote control set-
ting (see
page 156).
For wireless re-
mote controls:
Check connec-
tions, place remote
control unit close to
the boiler.
bF X Control mode Incorrect
LON commu-
nication mod-
ule
Replace LON com-
munication module
C1 X X Control mode Communica-
tion fault, ex-
tension EA1
Check connec-
tions
C2 X X Control mode Communica-
tion error, so-
lar control
module or
Vitosolic
Check solar control
module or
Vitosolic
C3 X X Control mode Communica-
tion fault, ex-
tension AM1
Check connec-
tions
C4 X X Control mode Communica-
tion fault,
OpenTherm
extension
Check OpenTherm
extension
Troubleshooting
Fault codes
(cont.)
5772 909 GB