Operating instructions

37
Supply pressure (flow pressure) Action
For natural gas For LPG
Below 17.4 mbar Below 25 mbar Do not start the boiler. Notify your gas
supply utility or LPG supplier.
17.4 to 25 mbar 25 to 47 mbar Start the boiler.
Above 25 mbar Above 47 mbar Contact your gas supplier if the supply
pressure is incorrect.
Function sequence and possible faults
Display Action
Control unit is-
sues a heat de-
mand
No
Increase set value
and ensure heat is
drawn off
Yes
Fan starts
No
After approx. 51 s,
fault F9
Check the fan, fan
connecting cables,
power at the fan
and fan control
Yes
Ignition
No
Fault EE
Check ignition
module (control
voltage 230 V
across plugs
"X2.1" and "X2.2").
Check the gas sup-
ply.
Yes
Gas train opens
No
Fault EE
Check the gas train
(control voltage
230 V) and gas
supply pressure
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5772 909 GB
Service