Coding in the delivered condition Possible change
Min. pump speed
E7:30 Minimum speed of the
variable speed heating
circuit pump: 30 % of the
max. speed (only for
weather-compensated
control units)
E7:0
to
E7:100
Minimum speed adjustable
from 0 to 100 % of the max-
imum speed
Screed drying
F1:0 Screed drying disabled
(only for weather-com-
pensated control units).
F1:1
to
F1:6
Screed drying adjustable in
accordance with 6 selecta-
ble temperature/time pro-
files (see page 151)
F1:15 Constant flow temperature
20 °C
Party mode time limit
F2:8 Time limit for party mode
or external heating pro-
gram changeover via but-
ton: 8 h (only for weather-
compensated control
units)
*1
F2:0 No time limit for party
mode
*1
F2:1
to
F2:12
Time limit adjustable from 1
to 12 h
*1
Pump control in "Only DHW"
F6:25 In the "Only DHW" oper-
ating mode, the internal
circulation pump is per-
manently on (only for
constant temperature
control units)
F6:0 In the "Only DHW" operat-
ing mode, the internal cir-
culation pump is perma-
nently off
F6:1
to
F6:24
In operating mode "DHW
only", the internal circula-
tion pump will be started 1
to 24 times per day for
10 min each time.
Pump control in "Standby mode"
F7:25 In "Standby mode", the
internal circulation pump
is permanently on (only
for constant temperature
control units)
F7:0 In "Standby mode", the in-
ternal circulation pump is
permanently off
F7:1
to
F7:24
In "Standby mode", the in-
ternal circulation pump will
be started 1 to 24 times per
day for 10 min each time.
*1
In the "Heating and DHW" program, party mode ends automatically when the
system changes over to operation with standard room temperature.
Code 1
"Heating circuit ..."/group 5
(cont.)