Operating instructions

74
Weather-compensated control unit Constant temperature control unit
Resetting all codes to their delivered condition
Select "Standard setting".
Note
This also resets codes at coding level 1.
Select "7" with Ú and confirm with OK.
When " " flashes, confirm with OK.
Note
This also resets codes at coding level 1.
"General"/group 1
Select "General" for weather-compen-
sated control units (see page 73).
Select "1" for constant temperature con-
trol units (see page 73).
Coding
Coding in the delivered condition Possible change
00:1 System version 1:
One heating circuit with-
out mixer A1 (heating cir-
cuit 1), without DHW
heating
00:2
to
00:10
For system schemes, see
the following table:
Value
address
00: ...
System
version
Description
2 1 One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
3 2, 3 One heating circuit with mixer M2 (heating circuit 2), without
DHW heating
4 2, 3 One heating circuit with mixer M2 (heating circuit 2), with
DHW heating
5 2, 3 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), without
DHW heating (code is adjusted automatically)
6 2, 3 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW
heating (code is adjusted automatically)
Code 2
Calling up coding level 2
(cont.)
5772 909 GB