Operating instructions
78
Coding in the delivered condition Possible change
3C:3 Function input DE3: Exter-
nal blocking.
Internal circulation pump
function: Coding address
3E
3C:4 Function input DE3: Exter-
nal blocking with fault mes-
sage input
Internal circulation pump
function: Coding address
3E
3C:5 Function input DE3: Fault
message input
3C:6 Function input DE3: Brief
operation, DHW circulation
pump (pushbutton func-
tion).
DHW circulation pump run-
time adjustment: Coding
address 3d
3d:5 DHW circulation pump
runtime for brief opera-
tion: 5 min
3d:1
to
3d:60
DHW circulation pump run-
time adjustable from 1 to
60 min
3E:0 Internal circulation pump
stays in control mode at
signal "External block-
ing"
3E:1 Internal circulation pump
stops at signal "External
blocking"
3E:2 Internal circulation pump
starts at signal "External
blocking"
3F:0 Internal circulation pump
stays in control mode at
signal "External de-
mand"
3F:1 Internal circulation pump
stops at signal "External
demand"
3F:2 Internal circulation pump
starts at signal "External
demand"
4b:0
Function input lH:
Room temperature con-
troller (Vitotrol 100). Only
for constant temperature
control units.
4b:1 External demand
4b:2 External blocking
Code 2
"General"/group 1
(cont.)
5772 909 GB