Technical information

4
Control Overview—External Controls Connections
LON Connections—System RJ45LON Adapter Overview
Applicable for Vitotronic 100, GC1, and Vitocontrol-S, RS/VB2
1 Vitocontrol-S, RS/VB2 system
control capable of
communicating with up to four
boiler controls Vitotronic 100,
KK10LON.
2 Installation of the RJ45 LON
Adaptor provides the ability to
interface the two wire
connection from the KK10LON
controls to the Vitocontrol-S,
RS/VB2. The adaptor and
Vitocontrol-S use CAT-5
connection cable supplied with
the adaptor. Refer to the RJ45
adaptor manual for specific
information.
3 Jumper settings on adaptor
board must be checked for
proper operation. Refer to the
specific manual for necessary
settings.
4 Communication connections to
KK10LON controls.
5 Verify the RJ45 Adaptor
jumpers have been set to
correspond with the system.
Jumpers JP1, JP2 and JP3
must be set to ON. This
configuration allows for a Free
BUS Topology with the adaptor
acting as the termination
resistor. Refer to adaptor
manual for detailed information.
1
2
3
5
Section 5.1
Section 5
Connection Overview
5346540 v1.0 09/2006 Technical information subject to change without notice