Technical information

Control Overview—Burner Control Wiring Diagnosis
Connection of Boiler Control Wiring to Burner (plug-in connection)
Applicable for Vitotronic 100, GC1
Section 6.1
Section 6
Control Harness Conduit
120VAC on L of [40] plug.
120VAC through S1 switch.
F2 fuse.
[151] plug jumper.
F6 Fixed high limit.
[150] plug terminal jumper across
12 and 15 (LWCO connection).
STB of 150 plug to L of [41]
plug.
L of [41] plug powers flame safe
guard of burner.
120VAC returns back to control
on BK3.
BK3 to T1 of [41] plug.
TR adjustable high limit.
K1 call-for-heat relay to TR/ON of
[150] plug.
Jumper across 17 and 16 of
[150] plug.
TR of [150] plug to T2 of [41]
plug.
T2 of [41] plug to burner and call-
for-heat.
120VAC Path Overview
CAUTION
!
This is a generic drawing only! Follow
the burner manufacturer’s
interconnection drawings for
interfacing burner with Viessmann
controls.
5346540 v1.0 09/2006 Technical information subject to change without notice