Technical information
Control Overview—Burner Control Wiring Diagnosis 
Connection of Boiler Control Wiring to Burner (hard-wired connection) 
Applicable for Vitotronic 100, GC1  
Section 6.1 
Section 6 
Control Harness Conduit 
•  120VAC on L of [40] plug. 
•  120VAC through S1 switch. 
•  F2 fuse. 
•  [151] plug jumper. 
•  F6 Fixed high limit. 
•  [150] plug terminal jumper across 
12 and 15 (LWCO connection). 
•  STB of 150 plug to L of [41] 
plug. 
•  L of [41] plug powers flame safe 
guard of burner. 
•  120VAC returns back to control 
on BK3. 
•  BK3 to T1 of [41] plug. 
•  TR adjustable high limit. 
•  K1 call-for-heat relay to TR/ON of 
[150] plug. 
•  Jumper across 17 and 16 of 
[150] plug. 
•  TR of [150] plug to T2 of [41] 
plug. 
•  T2 of [41] plug to burner and call-
for-heat. 
120VAC Path Overview 
CAUTION 
! 
This is a generic drawing only! Follow 
the burner manufacturer’s 
interconnection drawings for 
interfacing burner with Viessmann 
controls. 
5346540 v1.0 09/2006 Technical information subject to change without notice 
114 