Technical information
Control Overview—Burner Power Wiring
Connection of Boiler Power Wiring to Burner (hardwired connection)
Applicable for both Vitotronic 100, GC1 and 300, GW2
Flexible Conduit 208/460/575VAC, 3PH Supply
CAUTION
!
Refer to burner manual for correct
fuse and wire gauge sizing with
respect to burner electrical
requirements.
1 Incoming burner motor power
supply 208/460/575VAC, 3PH.
2 Connect 208/460/575VAC,
3PH power to terminals 21, 22
and 23 on DIN rail inside of
burner harness connection
enclosure.
3 DIN rail mounted female socket
inside boiler control junction
enclosure used for wiring burner
power.
4 Corresponding plug for burner
wiring is pre-wired for
termination in the burner and
plugs into receptacle mounted
on DIN rail. Refer to burner
manual for correct termination
inside of burner.
5 Burner contains motor starter
and blower motor.
1
2
4
3
5
Flexible Conduit
CAUTION
!
During start-up, check for correct
motor rotation. If motor rotates in the
opposite direction than indicated on
the burner, disconnect power supply
and reverse wires BK1 and BK2 on
the burner terminals.
Ensure work is carried out by only
qualified personnel.
Section 3.4
Section 3
Connection Overview
CAUTION
!
Provide disconnect means and over
current protection as required by local
codes
5346540 v1.0 09/2006 Technical information subject to change without notice