Technical information

Control Overview—External Controls Connections
BMS Connections—Burner Demand [146]
Applicable for Vitotronic 300, GW2
Burner Demand:
Dry contact to 146 plug terminals 2 and 3
Primary Consideration(s):
Burner operation can be started with override switch
Adjustable high limit and electronic limit settings will limit operation of
boiler/burner.
Configurations:
Boiler water temperature set point is determined by address 9b when
contact is closed on plug [146].
Electronic high limit is adjusted at address 06.
Burner switch-off differential adjusted at address 13.
Notes:
External demand only overrides outdoor reset calculation. Once the
contact at plug [146] is opened, the calculated boiler water temperature
will return to calculation from outdoor reset or DHW demand.
1 Boiler control.
2 Plug [146] used to interface
demand signal to control via
terminals 2 and 3. Open
contact removes burner
demand.
3 Field supplied relay and wiring
interconnections.
4 Field supplied relay to provide
burner demand when contact is
open between terminals 2 and
3.
Note: Relays used to provide dry
contact demand to plug [146[ is
controlled by local BMS or system
controller. The relay coil voltage
must be compatible with the
system that is controlling it. Some
examples of this are 24VAC,
120VAC and 24VDC.