Technical information

Control Overview—External Controls Connections
BMS Connections—Single Boiler—0-10VDC 145 KM-BUS
Applicable for Vitocontrol-S, CT3/VD2, MW1
1 Input Extension Module 0-10V
provides signal to boiler control
via 145 KM-BUS
2 Incoming 120VAC power
source.
3 Switched output
4 Control signal 0-10VDC from
BMS connected to plug [144].
5 Plug [145] KM-BUS
communication between input
module to boiler control. Field
wired and terminated in input
module and into [145] plug in
boiler control.
6 Connection of 145 KM BUS
communications within control.
IMPORTANT
Ensure that all field wiring conforms
to local codes and regulations.
40 157 144 145
1 2 3 1 2 3 1 2 3 L G N
2 3 4
6
5
1
IMPORTANT
Review manuals for specific
information regarding addressing,
values and detailed information.
CAUTION
!
When routing and running wiring for
communication between control
devices, there is the possibility of
electromagnetic interference. Avoid
running wires beside or near high
voltage 120/240VAC conductors.
IMPORTANT
If proximity to high voltage wires
cannot be avoided, use stranded,
twisted pair or shielded wire. Ensure
that only one end of wire is
grounded.
145
Section 4.4
Section 4
145
1 2 3
Connection Overview
5346540 v1.0 09/2006 Technical information subject to change without notice
97