Technical Data Manual for use by heating contractor Vitorond 200, VD2A Series Triple-pass hot water heating boiler 490 to 1096 MBH (144 to 321 kW) VITOROND 200 Product may not be exactly as shown Oil-/Gas-fired boiler triple-pass sectional cast iron design with Eutectoplex heat transfer surface and Therm-Control integrated low temperature protection logic for operation with modulating water temperatures Heating input: 490 to 1096 MBH (144 to 321 kW) 5354 787 - 01 04/2014
Product Information Vitorond 200, VD2A Technical Data Safety and Installation Requirements Please ensure that these instructions are read and understood before starting any service work. Failure to comply with these instructions may cause product/ property damage, severe personal injury and/or loss of life. Ensure that main power to the equipment being serviced is off. Working on the equipment Take precautions to avoid accidental activation of power or fuel during service work.
Vitorond 200, VD2A Technical Data Table of Contents Page Product Information Safety and Installation Requirements ............................2 Working on the equipment ......................................2 Product Information ....................................................2 VITOROND 200 .....................................................2 The benefits at a glance: ........................................2 Cross-Section ............................................................
Table of Contents Vitorond 200, VD2A Technical Data Page Standard Equipment Standard Equipment .................................................16 Standard equipment includes: ................................16 Boiler Control Boiler Control Alternatives .........................................17 For single-boiler installations:.................................17 Vitotronic 100, GC1/GC1B ...................................17 Vitotronic 300, GW2/GW2B ..................................
Vitorond 200, VD2A Technical Data Table of Contents Page System Design System Design Considerations ...................................23 Burner calibration .................................................23 In Canada ...........................................................23 In U.S.A. ............................................................23 Venting (option #1) ..............................................23 Chimney .............................................................
Product Information Vitorond 200, VD2A Technical Data Cross-Section Viessmann North America offers the side-mounted control option only. 6 E Low-emission burner (Weishaupt or Riello) F Second pass G Eutectoplex heat exchanger surface constructed from homogeneous special gray cast iron H Combustion chamber 5354 787 - 01 Legend A Extremely effective 4 in.
Technical Data Vitorond 200, VD2A Technical Data Technical Data Boiler Model VD2A- 125 160 195 230 270 Input (oil)*1 MBH (kW) 490 (144) 628 (184) 765 (224) 902 (264) 1059 (310) Input (gas)*1 MBH (kW) 508 (149) 650 (190) 792 (232) 934 (274) 1096 (321) Output (oil/gas)*2 MBH (kW) 433 (127) 553 (162) 672 (197) 794 (232) 932 (272) Combustion efficiency (oil) % 87.7 87.3 87.3 87.3 87.3 Combustion efficiency (gas) % 84.7 84.8 84.8 84.8 84.8 Thermal efficiency % 87.
Technical Data Vitorond 200, VD2A Technical Data Technical Data (continued) Boiler Model Weight Front section (with combustion chamber door) Intermediate section Rear section (with flue gas collar) Cast iron heat exchanger block Overall weight (complete with jacket, without burner) Boiler water content Max. boiler temperature*4 (= fixed high limit) Max. allow.
Technical Data Vitorond 200, VD2A Technical Data Technical Data (continued) Burner Installation 64 in. (1623 mm) *1 The burner must be fitted to the burner plate; installations direct to the boiler door are not feasible. Viessmann supplies a pre-drilled end burner plate in accordance with the supplied burner dimensions. Note: For mounting burners with blast tube diameters over 6 in. (150 mm), the door insulation (refractory material) can be cut to the required size.
Technical Data Vitorond 200, VD2A Technical Data Boiler Connection Kit (standard equipment) BWS LWCO SS 7¾ in. (195 mm) TG 57/8 in. (148 mm) 19e in. (490 mm) Dual Aquastat (optional) *1 9f in. (245 mm) Legend SS LWCO TG BWS Safety supply - connection to pressure relief valve Low water cut-off Temperature gauge Boiler water supply Note: Inch dimensions are rounded to the nearest 1/4 in. 10 9f in.
Technical Data Vitorond 200, VD2A Technical Data Clearances to Combustibles Boiler model VD2A- 125 160 195 230 Top 6 in. (150 mm) Sides 6 in. (150 mm) Flue (oil) 9 in. (229 mm) Flue (gas) 6 in. (150 mm) Front 6 in. (150 mm) Floor non-combustible Boiler model VD2Aa1 125 160 195 270 H Protect against frost and ensure good ventilation Otherwise, the system may suffer faults and damage.
Technical Data Vitorond 200, VD2A Technical Data Waterside Flow The Vitorond 200 boiler is designed for closed loop, forced circulation, hot water heating systems only. The recommended water flow rate through the Vitorond 200 is based on a temperature difference of between 20° F and 40° F (11° C and 22° C) (see table below).
Technical Data Vitorond 200, VD2A Technical Data Burner Calibration Weishaupt burners / Riello burners A Vitorond 200, VD2A boiler with a high-performance gas burner installed can achieve a thermal efficiency of up to 85.2%, and up to 87.
Technical Data Vitorond 200, VD2A Technical Data New Casting Design and Therm-Control Functionality A specific, matching boiler control is part of the standard equipment of the Vitorond 200, VD2A.
Technical Data Vitorond 200, VD2A Technical Data Therm-Control Low-Temperature Protection Logic A specific, matching boiler control is part of the standard equipment of the Vitorond 200, VD2A. Boiler protection is assured by the following: Example: Take a heating system with one heating circuit and a mixing valve. H Therm-Control logic In the start-up phase, the set Therm-Control temperature is not achieved at the Therm-Control sensor.
Standard Equipment Vitorond 200, VD2A Technical Data Standard Equipment Note: Boiler controls and burners are purchased separately. Please see Price List for details. H The cast iron sections are delivered as individual units on skids. H The combustion chamber door is mounted on the front section. H The flue gas collector, with two inspection opening covers (fastened with screws), is mounted on the rear section.
Boiler Control Vitorond 200, VD2A Technical Data Boiler Control Alternatives For single-boiler installations: Vitotronic 100, GC1/GC1B *1 For multiple-boiler installations: Vitotronic 100, GC1/GC1B *1 - Electronic boiler control unit for a constant boiler water temperature or weather-compensated operation in conjunction with a Vitocontrol panel with Vitotronic 300-K (type MW1S) or an external control unit Digital boiler control systems for modulating boiler and common supply temperature control.
Boiler Control Vitorond 200, VD2A Technical Data Boiler Control Alternatives (continued) Vitocontrol equipment for multiple-boiler system Legend A Up to 4 boilers with a Vitotronic 100, GC1/GC1B B Outside temperature sensor C Vitocontrol control panel with Vitotronic 300-K, MW1S/Vitotronic 300-K, MW1B D Flow temperature sensor Custom control panels For single-boiler or multiple-boiler installations: Vitotronic 100, GC1/GC1B *1 - Electronic boiler control unit - For two-stage or modulating burners - O
Boiler Control Vitorond 200, VD2A Technical Data Single-Boiler System: Vitorond 200, VD2A with Therm-Control Applications Heating system with manifold installed close to the boiler. The boiler water flow rate must be able to be reduced. Main components Single boiler system with: H Vitorond 200, VD2A, 125 to 270.
Boiler Control Vitorond 200, VD2A Technical Data Single-Boiler System: Vitorond 200, VD2A with Therm-Control (continued) Installation Example Plug Outdoor temperature sensor (only for Vitotronic 200 HK1M/HK1B and Vitotronic 300 GW2/GW2B) ?M2 Flow temperature sensor, mixing valve (only for the Vitotronic 300 GW2/GW2B) ?M3 Flow temperature sensor, mixing valve § Boiler water temperature sensor % DHW tank temperature sensor (accessory for the Vitotronic 100 GC1/GC1B) aJA Therm-Control temperature sensor sÖM
Boiler Control Vitorond 200, VD2A Technical Data Multi-Boiler System: Vitorond 200, VD2A with Therm-Control Applications Heating system with manifold installed close to the boiler. The boiler water flow rate will be reduced via the motorized butterfly valve. Main components Multi-boiler system with: H Vitorond 200, VD2A, 125 to 270.
Boiler Control Vitorond 200, VD2A Technical Data Multi-Boiler System, Vitorond 200, VD2A with Therm-Control (continued) Installation Example Plug Outdoor temperature sensor (only for Vitocontrol-S MW1/Vitotronic 300-K, MW1B) ?Flow Flow temperature sensor, common heating flow (only for Vitocontrol-S MW1/Vitotronic 300-K, MW1B) ?M2 Flow temperature sensor, mixing valve (only for Vitocontrol-S MW1/Vitotronic 300-K, MW1B) ?M3 Flow temperature sensor, mixing valve (only for Vitocontrol-S MW1/Vitotronic 300-K,
System Design Vitorond 200, VD2A Technical Data System Design Considerations Burner calibration Venting (option #1) With 2-stage and fully modulating burners, ensure that the chimney is compatible with the lower flue gas temperatures associated with partial load conditions set on the burner. The Vitorond 200, VD2A boiler is approved as a Category I appliance and must be vented accordingly. WARNING When installing or insulating (overhead) piping or venting, do not stand on top panel of boiler.
System Design Vitorond 200, VD2A Technical Data System Design Considerations (continued) Barometric draft regulator type Venting (option #2) For natural gas or propane applications, use a doubleacting type. The Vitorond 200 boiler is a Category III positive pressure non-condensing boiler. For #2 fuel oil applications, use a single-acting type. Each boiler must be vented individually.
System Design Vitorond 200, VD2A Technical Data System Design Considerations (continued) Combustion air supply Water quality and freeze protection The boiler must not be located in areas or rooms where chemicals containing chlorine, bromine, fluorine, or other corrosive chemicals are stored. Examples include refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents, water softener salt, etc. The combustion air must not be contaminated with any amount of the above mentioned chemicals.
System Design Vitorond 200, VD2A Technical Data System Design Considerations (continued) Sound attenuation Anti-vibration measures Please consult a professional engineer who is specialized in noise attenuation for advice. Anti-vibration supports can be field supplied as an economical and effective solution to combat noise generated. The burner/boiler systems, circulation pumps and other auxiliary equipment used in heating systems generate noise.
Burner Vitorond 200, VD2A Technical Data Burner Alternatives Weishaupt Burners - Linkageless Boiler model VD2A- 125 160 195 230 270 No. 2 oil-fired Model WL20 WL30 Model WG20 - LN WG30 - LN Model WG20 - LN WG30 - LN Model WG20 - LN WG30 - LN Model WG20 - LN WG30 - LN 2-stage Natural gas-fired 2-stage Natural gas-fired fully modulating Propane gas-fired 2-stage Propane gas-fired fully modulating Riello Burners Boiler model VD2A- No.
5354 787 - 01 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.