Operating instructions

108
Delivered condition 0
Setting 1 / 0
2006/2007 Heating curve slope/level
"Heating curve slope 2006"
"Heating curve level 2007"
Heating curve level and slope for all
heating circuits (A1, M2).
Operating instructions
Heating curve level
2007
Heating curve slope 2006
Delivered condition
0 ( 0 K) 12 ( 1.2)
Setting range
–150 to +400 ( –15 to +
40 K)
0 to 35 ( 0 to 3.5)
200A Influence of room temperature hook-up
"Slope room hook-up 200A"
The influence of room temperature hook-
up can be selected, subject to a room
temperature sensor being installed and
room temperature hook-up being ena-
bled (see page 108).
The higher the value, the greater the
influence of the room temperature on the
set flow temperature of the relevant heat-
ing circuit with weather-compensated
control.
Delivered condition 10
Setting range 0 to 50
200B Room temperature hook-up (heating circuits)
"Room temperature hook-up 200B"
Parameter group heating circuits/cooling circuit
2003 Enabling the remote control
(cont.)
5441 603 GB